Heat Pump List

Tools

Denali Aire heat pumps

8 certified models, ranked by seasonal cooling efficiency (SEER2), then heating efficiency (HSPF2), highest first.

Filters

Filters Denali Aire

The list

  1. 1 2DNMSHQCO9ADenali Aire
    9,000 Btu/hheating at 47°F 9,000 Btu/hcooling at 95°F

    9,000 Btu · Mini-split · 5°F 8,700 Btu/h · Cold output 77–97% · HSPF2 9.8 · 2 pairings

  2. 2 2DNMSHQCO24Denali Aire
    24,000 Btu/hheating at 47°F 24,000 Btu/hcooling at 95°F

    24,000 Btu (2-ton) · Mini-split · 5°F 19,200 Btu/h · Cold output 80–83% · HSPF2 9.5 · 2 pairings

  3. 3 DNMSHQCO18Denali Aire
    18,000 Btu/hheating at 47°F 18,000 Btu/hcooling at 95°F

    18,000 Btu (1.5-ton) · Mini-split · 5°F 12,700 Btu/h · Cold output 71% · HSPF2 8.6 · 1 pairing

  4. 4 2DNMSHQCO12ADenali Aire
    12,000 Btu/hheating at 47°F 12,000 Btu/hcooling at 95°F

    12,000 Btu (1-ton) · Mini-split · 5°F 9,200 Btu/h · Cold output 77% · HSPF2 9.5 · 2 pairings

  5. 5 DNMSHQCO12ADenali Aire
    12,000 Btu/hheating at 47°F 12,000 Btu/hcooling at 95°F

    12,000 Btu (1-ton) · Mini-split · 5°F 8,400 Btu/h · Cold output 70% · HSPF2 9.5 · 1 pairing

  6. 6 2DNMSHQCO18Denali Aire
    18,000 Btu/hheating at 47°F 18,000 Btu/hcooling at 95°F

    18,000 Btu (1.5-ton) · Mini-split · 5°F 18,000 Btu/h · Cold output 100% · HSPF2 9.8 · 2 pairings

  7. 7 DNMSHQCO24Denali Aire
    23,000 Btu/hheating at 47°F 23,000 Btu/hcooling at 95°F

    24,000 Btu (2-ton) · Mini-split · 5°F 18,000 Btu/h · Cold output 78% · HSPF2 8.6 · 1 pairing

  8. 8 DNMSHQCO9ADenali Aire
    9,000 Btu/hheating at 47°F 9,000 Btu/hcooling at 95°F

    9,000 Btu · Mini-split · 5°F 6,300 Btu/h · Cold output 70% · HSPF2 9.0 · 1 pairing

Denali Aire heat pumps, ranked by seasonal cooling efficiency (SEER2), then heating efficiency (HSPF2)
# Model Brands Type Size At 5°FBtu/h · heating At 47°FBtu/h · heating At 95°FBtu/h · cooling Cold output% of 47°F rating COP 5°Ffull speed SEER2median pairing HSPF2Btu/Wh · median pairing Compressor Refrigerant Market Pairings
1 2DNMSHQCO9A Denali Aire Mini-split 9,000 Btu8,700 9,000 9,000 77–97% 1.90 22.5 9.8 Variable R-454B US CA 2
2 2DNMSHQCO24 Denali Aire Mini-split 24,000 Btu (2-ton)19,200 24,000 24,000 80–83% 1.90 22.5 9.5 Variable R-454B US CA 2
3 DNMSHQCO18 Denali Aire Mini-split 18,000 Btu (1.5-ton)12,700 18,000 18,000 71% 1.80 22.5 8.6 Variable R-410A US CA 1
4 2DNMSHQCO12A Denali Aire Mini-split 12,000 Btu (1-ton)9,200 12,000 12,000 77% 1.90 22.0 9.5 Variable R-454B US CA 2
5 DNMSHQCO12A Denali Aire Mini-split 12,000 Btu (1-ton)8,400 12,000 12,000 70% 1.75 21.7 9.5 Variable R-410A US CA 1
6 2DNMSHQCO18 Denali Aire Mini-split 18,000 Btu (1.5-ton)18,000 18,000 18,000 100% 1.90 21.0 9.8 Variable R-454B US CA 2
7 DNMSHQCO24 Denali Aire Mini-split 24,000 Btu (2-ton)18,000 23,000 23,000 78% 1.75 20.5 8.6 Variable R-410A US CA 1
8 DNMSHQCO9A Denali Aire Mini-split 9,000 Btu6,300 9,000 9,000 70% 1.80 18.5 9.0 Variable R-410A US CA 1

The share is heat output at 5°F divided by the 47°F rating. Tests use different compressor speeds.

8 of 8 units

Other sizes

Every size class, with how many units it holds and its median heat output at 5°F