Heat Pump List

Tools

FOP1460TJAYNA

FOP1460TJAYNA is in the certified data.

Its certified ratings are 7.8 HSPF2 and 15.2 SEER2.

Fujitsu · central heat pump

FOP1460TJAYNA is in the certified data as of Sep 19, 2026.

4 certified pairings with 2 different figures. See all

Certified heating and cooling

Heating at 47°F

55,500

34,200 at 17°F

NR at 5°F

Btu/h, certified

NR COP at 5°F

Cooling at 95°F

55,500

Btu/h, certified

EER2 11.7 at 95°F

SEER2 15.2

Heating and cooling by outdoor temperature

Certified heating at 5, 17, and 47°F and cooling at 95°F for FOP1460TJAYNA, by outdoor temperature Heating: no certified figure at 5°F, 34,200 Btu/h at 17°F, 55,500 Btu/h at 47°F. Cooling: 55,500 Btu/h at 95°F. The bars start at zero. Median of 4.5-ton central models: 40,000 Btu/h at 5°F, 37,800 Btu/h at 17°F, 56,000 Btu/h at 47°F, 55,000 Btu/h at 95°F. 0 20,000 40,000 60,000 Btu/h NR 5°F 34,200 17°F 55,500 47°F 55,500 95°F Outdoor temperature (°F)
  • Heating output
  • Cooling output
  • Median of 4.5-ton central models
  • Example heating load
  • Example cooling load
  • Frosting range, 17 to 45°F

This pairing delivers 55,500 Btu/h of heat at 47°F and 34,200 Btu/h at 17°F. It delivers 55,500 Btu/h of cooling at 95°F. At 95°F that is 35,500 Btu/h above the example cooling load of 20,000 Btu/h.

Each bar is a separate certified test, drawn at its outdoor temperature, starting at zero. The 47°F figure is at high stage; the 17 and 5°F figures are at full speed. The short dark line on each bar is the median of 4.5-ton central models, one value per model. The shaded 17 to 45°F band is the frosting range: the outdoor coil can frost, and the unit pauses to defrost.

The dashed lines are example loads for a typical area of about 1,650 sq ft where winters reach 5°F: heating runs from 40,000 Btu/h at 5°F to 0 at 65°F, and cooling runs from 0 at 65°F to 20,000 Btu/h at 95°F, at 1,000 sq ft per ton. A house in a hot climate or with large west-facing windows can need twice as much cooling. They are examples, not your building.

Calculate heating and cooling for your house

AHRI certificate 214604164 · listed by Fujitsu · certified May 2, 2024 · 3 pairings share these values

All rebate programs and their published thresholds

Certified output and power use

Certified output for the selected pairingThe four bars share one scale. The comparison is with the median of 4.5-ton central models. Heating tests run at 70°F indoors. The cooling test runs at 80°F indoors.
Outdoor temperature Certified outputBtu/h One scale vs class median COPat 5°F
5°Ffull speed NR NR NR
17°Ffull speed 34,20010.02 kW −10% NR
47°Fhigh stage 55,50016.27 kW −1% NR
95°Fcooling, full load 55,50016.27 kW — NR

EER2 11.7 in that test. SEER2 15.2 over the modeled cooling season.

Power use at each temperature

Electrical input in the 5°F full-speed test
NRkW
Electrical input in the 95°F cooling test
4.74kW
Seasonal average heating COP
2.29

These exclude backup resistance heat.

Updated Sep 19, 2026 · Methodology

How it compares with other 54,000 Btu heat pumps

4.5-ton central models

This pairing at 5°F
NR
This unit at 5°F median across its pairings
NR
Median of 4.5-ton central models at 5°F
40,000 Btu/h
Models in this group
343

This size class is defined by cooling capacity, so cooling is not compared here.

Every 54,000 Btu (4.5-ton) unit, ranked by cooling efficiency, then heating efficiency

Certified values for FOP1460TJAYNA

4 pairings · 4 AHRI certificates

This pairing is the one shown above. Under all pairings, a single figure means every pairing agrees and a range means the pairing decides.

Certified values for FOP1460TJAYNA
This pairingAll pairings
Heating
Heat output at 47°F high stage 55,500 Btu/h 55,500 Btu/h
Heat output at 17°F full speed 34,200 Btu/h 34,000–34,200 Btu/h
Heat output at 5°F full speed NR NR
Heat output below 5°F NR NR
Cold output 5°F output as a % of the 47°F rating NR NR
COP at 5°F full speed NR —
HSPF2 Region IV 7.8 7.8
Cooling
Cooling capacity at 95°F full-load test 55,500 Btu/h 55,500–57,000 Btu/h
EER2 at 95°F 11.7 11.7
SEER2 cooling season 15.2 15.2
Cooling at other temperatures NR NR
Equipment and listing
Refrigerant R-454B
Compressor Two-stage
Indoor unit FCCA6021SYTA 2 indoor units
FurnaceFF80SV510021UHS 4 furnaces
Cold-climate designation EPA's designation, as published NC NC
ENERGY STAR Most Efficient EPA's designation, as published No On no pairings
Where it is sold US and Canada US and Canada
Model string as certified FOP1460TJAYNA

Pairings, by indoor-unit class

2 indoor units · 4 certified pairings

One row per indoor unit certified with this outdoor unit.

Furnace paired · 2 indoor units

  1. FCCA6021SYTA (the pairing on screen) brand not stated NRat 5°F, full speed

    3 pairings, 3 with a furnace · 47°F 55,500 Btu/h · 95°F cooling 55,500 Btu/h · Cold output NR · COP —

  2. FCCN6024SYTA brand not stated NRat 5°F, full speed

    1 pairing, 1 with a furnace · 47°F 55,500 Btu/h · 95°F cooling 57,000 Btu/h · Cold output NR · COP —

Indoor units in the furnace paired class
Indoor unit Brand At 5°FBtu/h · full speed At 47°FBtu/h · high stage At 95°FBtu/h · cooling Cold output% of 47°F rating COP 5°Ffull speed Cold climate Pairings
FCCA6021SYTA (the pairing on screen) — NR 55,500 55,500 NR — NC 3
FCCN6024SYTA — NR 55,500 57,000 NR — NC 1

The share is heat output at 5°F divided by the 47°F rating. Tests use different compressor speeds.

Showing 2 of 2 indoor units

Sold as, and units with identical certified values

Brands listing this model number

Model number as listed

History and definitions

History

First certified record
Most recent certified record
Measurements reported
May 2, 2024
Status
In the certified data

Field definitions

COP
Heat delivered for each unit of electricity used. A COP of 2.5 gives 2.5 times the heat of an electric baseboard heater.
HSPF2
Heating efficiency over a typical season. Higher uses less electricity.
SEER2
Cooling efficiency over a typical season. Higher uses less electricity.
EER2
Cooling output divided by electrical input in the 95°F full-load test, in Btu/h per watt.
Cold output
Heat output at 5°F as a percentage of the 47°F rating.
% of rating at 17°F
Heat output at 17°F as a percentage of the 47°F rating.

NR not in the certified dataNC not cold-climate certifiedSP single pairing onlyVP varies by pairing; see the pairings tableWD withdrawn since the certified data was last read

Cite or print this page

Heat Pump List, “FOP1460TJAYNA — certified heat output”. Certified figures dated , checked daily.
https://heatpumplist.com/model/fop1460tjayna