N5HP5018A1 is in the certified data.

Its certified full-speed heating output at 5°F is 8,900 Btu/h, 52–53% of its 47°F rating, depending on the pairing.

American Standard and Trane · central heat pump

N5HP5018A1 is in the certified data as of Sep 19, 2026.

8 certified pairings with 2 different figures. See all

Certified heating and cooling

Heating at 47°F

16,800

11,500 at 17°F

8,900 at 5°F

Btu/h, certified

2.11 COP at 5°F

Cooling at 95°F

18,300

Btu/h, certified

EER2 12.0 at 95°F

SEER2 15.2

Heating and cooling by outdoor temperature

Certified heating at 5, 17, and 47°F and cooling at 95°F for N5HP5018A1, by outdoor temperature Heating: 8,900 Btu/h at 5°F, 11,500 Btu/h at 17°F, 16,800 Btu/h at 47°F. Cooling: 18,300 Btu/h at 95°F. The bars start at zero. Median of 1.5-ton central models: 11,200 Btu/h at 5°F, 12,600 Btu/h at 17°F, 18,000 Btu/h at 47°F, 18,000 Btu/h at 95°F. 0 5,000 10,000 15,000 20,000 Btu/h 8,900 5°F 11,500 17°F 16,800 47°F 18,300 95°F Outdoor temperature (°F)
  • Heating output
  • Cooling output
  • Median of 1.5-ton central models
  • Example heating load
  • Example cooling load
  • Frosting range, 17 to 45°F

This pairing delivers 16,800 Btu/h of heat at 47°F, 11,500 Btu/h at 17°F, and 8,900 Btu/h at 5°F, 53% of its 47°F rating. It delivers 18,300 Btu/h of cooling at 95°F. At 5°F that is 2,100 Btu/h short of the example heating load of 11,000 Btu/h; at 95°F it is 12,800 Btu/h above the example cooling load of 5,500 Btu/h.

Each bar is a separate certified test, drawn at its outdoor temperature, starting at zero. The 47°F figure is at one speed; the 17 and 5°F figures are at full speed. The short dark line on each bar is the median of 1.5-ton central models, one value per model. The shaded 17 to 45°F band is the frosting range: the outdoor coil can frost, and the unit pauses to defrost.

The dashed lines are example loads for a typical area of about 450 sq ft where winters reach 5°F: heating runs from 11,000 Btu/h at 5°F to 0 at 65°F, and cooling runs from 0 at 65°F to 5,500 Btu/h at 95°F, at 1,000 sq ft per ton. A house in a hot climate or with large west-facing windows can need twice as much cooling. They are examples, not your building.

Calculate heating and cooling for your house

AHRI certificate 218469946 · listed by Trane · certified Jun 29, 2026 · 4 pairings share these values

All rebate programs and their published thresholds

Certified output and power use

Certified output for the selected pairingThe four bars share one scale. The comparison is with the median of 1.5-ton central models. Heating tests run at 70°F indoors. The cooling test runs at 80°F indoors.
Outdoor temperature Certified outputBtu/h One scale vs class median COPat 5°F
5°Fone compressor speed 8,9002.61 kW −21% 2.11
17°Fone compressor speed 11,5003.37 kW −9% NR
47°Fone compressor speed 16,8004.92 kW −7% NR
95°Fcooling, full load 18,3005.36 kW — NR

EER2 12.0 in that test. SEER2 15.2 over the modeled cooling season.

Power use at each temperature

Electrical input in the 5°F full-speed test
1.24kW
Electrical input in the 95°F cooling test
1.53kW
Seasonal average heating COP
2.34

These exclude backup resistance heat.

Updated Sep 19, 2026 · Methodology

How it compares with other 18,000 Btu heat pumps

1.5-ton central models

This pairing at 5°F
8,900 Btu/h
This unit at 5°F median across its pairings
8,900 Btu/h
Median of 1.5-ton central models at 5°F
11,200 Btu/h
Models in this group
243

This unit is above 30% of them, at number 171 of 243 by heat at 5°F. The middle half of the group runs 8,600 to 18,000 Btu/h.

This size class is defined by cooling capacity, so cooling is not compared here.

Closest models by heat at 5°F

Every 18,000 Btu (1.5-ton) unit, ranked by cooling efficiency, then heating efficiency

Certified values for N5HP5018A1

8 pairings · 8 AHRI certificates

This pairing is the one shown above. Under all pairings, a single figure means every pairing agrees and a range means the pairing decides.

Certified values for N5HP5018A1
This pairingAll pairings
Heating
Heat output at 47°F one speed 16,800 Btu/h 16,800–17,000 Btu/h
Heat output at 17°F full speed 11,500 Btu/h 11,500–11,600 Btu/h
Heat output at 5°F full speed 8,900 Btu/h 8,900 Btu/h
Heat output below 5°F NR NR
Cold output 5°F output as a % of the 47°F rating 53%
COP at 5°F full speed 2.11 2.09–2.11
HSPF2 Region IV 8.0 8.0
Cooling
Cooling capacity at 95°F full-load test 18,300 Btu/h 18,300–18,500 Btu/h
EER2 at 95°F 12.0 12.0
SEER2 cooling season 15.2 15.2
Cooling at other temperatures NR NR
Equipment and listing
Refrigerant R-454B
Compressor Single stage
Indoor unit 5PX*B006AS3+TSTAT 2 indoor units
FurnaceA952V060BD3SB 2 furnaces
Cold-climate designation EPA's designation, as published NC NC
ENERGY STAR Most Efficient EPA's designation, as published No On no pairings
Where it is sold United States United States
Model string as certified N5HP5018A1

Pairings, by indoor-unit class

2 indoor units · 8 certified pairings

One row per indoor unit certified with this outdoor unit.

Furnace paired · 2 indoor units

  1. 5PX*B006AS3+TSTAT (the pairing on screen) brand not stated 8,900 Btu/hat 5°F, full speed

    4 pairings, 2 with a furnace · 47°F 16,900 Btu/h · 95°F cooling 18,400 Btu/h · Cold output 53% · COP 2.10

  2. 5TXCB006AS3+TSTAT brand not stated 8,900 Btu/hat 5°F, full speed

    4 pairings, 2 with a furnace · 47°F 16,900 Btu/h · 95°F cooling 18,400 Btu/h · Cold output 53% · COP 2.10

Indoor units in the furnace paired class
Indoor unit Brand At 5°FBtu/h · full speed At 47°FBtu/h · one speed At 95°FBtu/h · cooling Cold output% of 47°F rating COP 5°Ffull speed Cold climate Pairings
5PX*B006AS3+TSTAT (the pairing on screen) — 8,900 16,900 18,400 53% 2.10 NC 4
5TXCB006AS3+TSTAT — 8,900 16,900 18,400 53% 2.10 NC 4

The share is heat output at 5°F divided by the 47°F rating.

Showing 2 of 2 indoor units

Sold as, and units with identical certified values

Brands listing this model number

Other brands that list these model numbers

Model number as listed

History and definitions

History

First certified record
Most recent certified record
Measurements reported
Jun 29, 2026
Status
In the certified data

Field definitions

COP
Heat delivered for each unit of electricity used. A COP of 2.5 gives 2.5 times the heat of an electric baseboard heater.
HSPF2
Heating efficiency over a typical season. Higher uses less electricity.
SEER2
Cooling efficiency over a typical season. Higher uses less electricity.
EER2
Cooling output divided by electrical input in the 95°F full-load test, in Btu/h per watt.
Cold output
Heat output at 5°F as a percentage of the 47°F rating.
% of rating at 17°F
Heat output at 17°F as a percentage of the 47°F rating.

NR not in the certified dataNC not cold-climate certifiedSP single pairing onlyVP varies by pairing; see the pairings tableWD withdrawn since the certified data was last read