TC-12CHRH/DVO-D
Rovsun · mini-split heat pump
All 30 certified Rovsun models
TC-12CHRH/DVO-D is in the certified data as of Sep 19, 2026. TC-12CHRH/DVO-D changed its certified SEER2 on AHRI certificate 217154248 from 18.5 to 19.0 in the certified data between August 2025 and September 2026.
- 12,000 Btu (1-ton)
- Mini-split
- Variable speed
- US and Canada
Certified heating and cooling
Heating at 47°F
12,0003.52NR
No 47°F rating for this pairing.
10,2002.99NR at 17°F
8,8002.58NR at 5°F
Btu/hkW, certified
1.80NR COP at 5°F
Heating and cooling by outdoor temperature
This pairing delivers 12,000 Btu/h3.52 kW of heat at 47°F, 10,200 Btu/h2.99 kW at 17°F, and 8,800 Btu/h2.58 kW at 5°F, 73% of its 47°F rating. It delivers 11,000 Btu/h3.22 kW of cooling at 95°F. At 5°F that is 200 Btu/h0.06 kW short of the example heating load of 9,000 Btu/h2.64 kW; at 95°F it is 6,000 Btu/h1.76 kW above the example cooling load of 5,000 Btu/h1.47 kW.
Each bar is a separate certified test, drawn at its outdoor temperature, starting at zero. The 47°F figure is at normal speed; the 17 and 5°F figures are at full speed. The short dark line on each bar is the median of 1-ton mini-split models, one value per model. The shaded 17 to 45°F band is the frosting range: the outdoor coil can frost, and the unit pauses to defrost.
The dashed lines are example loads for a typical area of about 400 sq ft where winters reach 5°F: heating runs from 9,000 Btu/h2.64 kW at 5°F to 0 at 65°F, and cooling runs from 0 at 65°F to 5,000 Btu/h1.47 kW at 95°F, at 1,000 sq ft per ton. A house in a hot climate or with large west-facing windows can need twice as much cooling. They are examples, not your building.
AHRI certificate 217154248 · listed by ROVSUN · certified Sep 25, 2025 · 1 pairing carries these values
Certified output and power use
| Outdoor temperature | Certified outputBtu/h | One scale | vs class median | COPat 5°F |
|---|---|---|---|---|
| 5°Ffull speed | 8,8002.58 kW | −4% | 1.80 | |
| 17°Ffull speed | 10,2002.99 kW | +4% | NR | |
| 47°Fnormal speed | 12,0003.52 kW | 0% | NR | |
| 95°Fcooling, full load | 11,0003.22 kW | — | NR |
EER2 11.0 in that test. SEER2 19.0 over the modeled cooling season.
Power use at each temperature
- Electrical input in the 5°F full-speed test
- 1.43kW
- Electrical input in the 95°F cooling test
- 1.00kW
- Seasonal average heating COP
- 2.46
These exclude backup resistance heat.
How it compares with other 12,000 Btu heat pumps
1-ton mini-split models
- This pairing at 5°F
- 8,800 Btu/h2.58 kWNR
- This unit at 5°F median across its pairings
- 8,800 Btu/h2.58 kW
- Median of 1-ton mini-split models at 5°F
- 9,200 Btu/h2.70 kW
- Models in this group
- 888
This unit is above 35% of them, at number 580 of 888 by heat at 5°F. The middle half of the group runs 8,400 to 11,300 Btu/h.
Among 12,000 Btu mini-split models, each by its median certified pairing, highest first: 5°F output as a share of its 47°F rating, 489th of 887 (tied); HSPF2, 887th of 895 (tied). Models without that figure are left out.
Similar ratings at 47°F
These mini-split models share the nominal cooling size. Comparisons use each model’s median certified figures across pairings.
- BM12YDIY22C: The same 12,000 Btu/h rating at 47°F; 46,000 Btu/h at 5°F (this model: 8,800).
- AOUG12LZAH1: The same 12,000 Btu/h rating at 47°F; 16,600 Btu/h at 5°F (this model: 8,800).
- AOUH12LUAS1: The same 12,000 Btu/h rating at 47°F; 15,500 Btu/h at 5°F (this model: 8,800).
Closest models by heat at 5°F
- GWH12AGCXD-A3DNA1A/OGree · 8,800 Btu/h
- H12SAH20BQCTCL · 8,800 Btu/h
- SAK-12-DT2/220VStar Air Kontrol · 8,800 Btu/h
- 1U12EH2HEHaier · 8,700 Btu/h
- FH12QCA3DI-20USAufit · 8,700 Btu/h
- YN012ALFI22RPDPioneer · 8,700 Btu/h
Every 12,000 Btu (1-ton) unit, ranked by cooling efficiency, then heating efficiency
Floor area at the cold test point
The median certified output of 8,800 Btu/h at 5°F matches the size calculator’s heating estimate for these floor areas, rounded to about 10 sq ft. Each range divides that output by the climate band’s heating rates.
| Climate band | House condition | Btu/h per sq ft | Approximate sq ft |
|---|---|---|---|
| Mild | Drafty, little insulation | 24–42 | 210–370 |
| Mild | Typical | 16–26 | 340–550 |
| Mild | Tight, well insulated | 10–18 | 490–880 |
| Cold | Drafty, little insulation | 28–52 | 170–310 |
| Cold | Typical | 18–30 | 290–490 |
| Cold | Tight, well insulated | 12–22 | 400–730 |
| Very cold | Drafty, little insulation | 32–58 | 150–280 |
| Very cold | Typical | 22–38 | 230–400 |
| Very cold | Tight, well insulated | 16–28 | 310–550 |
This is an estimate, not a house-specific load calculation. Output stays at the 5°F test point for every band; it does not predict output at the band’s winter design temperature.
Certified values for TC-12CHRH/DVO-D
1 pairing · 1 AHRI certificate
This pairing is the one shown above. Under all pairings, a single figure means every pairing agrees and a range means the pairing decides.
| This pairing | All pairings | |
|---|---|---|
| Heating | ||
| Heat output at 47°F normal speed | 12,000 Btu/h3.52 kWNR | 12,000 Btu/h3.52 kW |
| Heat output at 17°F full speed | 10,200 Btu/h2.99 kWNR | 10,200 Btu/h2.99 kW |
| Heat output at 5°F full speed | 8,800 Btu/h2.58 kWNR | 8,800 Btu/h2.58 kW |
| Heat output below 5°F | NR | NR |
| Cold output 5°F output as a % of the 47°F rating | 73%NR | |
| COP at 5°F full speed | 1.80NR | 1.80 |
| HSPF2 Region IV | 8.4NR | 8.4 |
| Cooling | ||
| Cooling capacity at 95°F full-load test | 11,000 Btu/h3.22 kWNR | 11,000 Btu/h3.22 kW |
| EER2 at 95°F | 11.0NR | 11.0 |
| SEER2 cooling season | 19.0NR | 19.0 |
| Cooling at other temperatures | NR | NR |
| Equipment and listing | ||
| Refrigerant | R-454B | |
| Compressor | Variable speed | |
| Indoor unit | None listed | None |
| Furnace | No furnace | None |
| Cold-climate designation EPA's designation, as published | Yes | On every pairing |
| ENERGY STAR Most Efficient EPA's designation, as published | No | On no pairings |
| Where it is sold | US and Canada | US and Canada |
| Model string as certified | TC-12CHRH/DVO-D | |
Pairings, by indoor-unit class
1 certified pairing
One row per indoor unit certified with this outdoor unit.
Ductless indoor
-
None listed (the pairing on screen) Rovsun 8,800 Btu/h2.58 kWat 5°F, full speed
| Indoor unit | Brand | At 5°FBtu/hkW · full speed | At 47°FBtu/hkW · normal speed | At 95°FBtu/hkW · cooling | Cold output% of 47°F rating | COP 5°Ffull speed | Cold climate | Pairings |
|---|---|---|---|---|---|---|---|---|
| None listed (the pairing on screen) | Rovsun | 8,8002.58 | 12,0003.52 | 11,0003.22 | 73% | 1.80 | Yes | 1 |
Sold as, and units with identical certified values
Variants of the same model number
3 units in this group. Basis: identical certified values in the certified data. This grouping is our inference, not a field in the certified data.
2 of 3 shown.
Other model numbers with identical certified values
3 units share this record. Basis: identical certified values in the certified data. This grouping is our inference, not a field in the certified data.
2 of 3 shown.
What affects the price
We don't have prices. These things drive the cost.
- The size of the unit, and the indoor equipment on the same certificate.
- Whether existing ductwork is reused, altered, or replaced.
- The electrical work: a circuit, a disconnect, and sometimes a panel change.
- Refrigerant line length and how the outdoor unit is mounted.
- Permits and inspection, which vary by municipality.
- Removing and disposing of the old equipment.
- Local labor rates and how busy the season is.
- Rebates and tax credits, which change and have deadlines.
Product history
- TC-12CHRH/DVO-D changed its certified SEER2 on AHRI certificate 217154248 from 18.5 to 19.0 in the certified data between August 2025 and September 2026.
- TC-12CHRH/DVO-D changed its certified HSPF2 on AHRI certificate 217154248 from 8.5 to 8.4 in the certified data between August 2025 and September 2026.
- TC-12CHRH/DVO-D changed its certified EER2 on AHRI certificate 217154248 from 11.7 to 11.0 in the certified data between August 2025 and September 2026.
- TC-12CHRH/DVO-D changed its certified heat output at 47°F on AHRI certificate 217154248 from 11,000 Btu/h to 12,000 Btu/h in the certified data between August 2025 and September 2026.
- TC-12CHRH/DVO-D changed its certified heat output at 17°F on AHRI certificate 217154248 from 7,400 Btu/h to 10,200 Btu/h in the certified data between August 2025 and September 2026.
- TC-12CHRH/DVO-D first appeared in the certified data between March 2025 and May 2025.
History and definitions
Other CASSETTE-single models by nominal cooling size: TC-12CHRH/DVO (12,000 Btu), TMSC-18HA2/I2XI20B-O (15,000 Btu), RV-18M2/O-R (18,000 Btu), RVC-24/O (24,000 Btu), TC-24CHRH/DVO (24,000 Btu).
History
- First certified record
- Most recent certified record
- Measurements reported
- Sep 25, 2025
- Status
- In the certified data
Field definitions
- COP
- Heat delivered for each unit of electricity used. A COP of 2.5 gives 2.5 times the heat of an electric baseboard heater.
- HSPF2
- Heating efficiency over a typical season. Higher uses less electricity.
- SEER2
- Cooling efficiency over a typical season. Higher uses less electricity.
- EER2
- Cooling output divided by electrical input in the 95°F full-load test, in Btu/h per watt.
- Cold output
- Heat output at 5°F as a percentage of the 47°F rating.
- % of rating at 17°F
- Heat output at 17°F as a percentage of the 47°F rating.
NR not in the certified dataNC not cold-climate certifiedSP single pairing onlyVP varies by pairing; see the pairings tableWD withdrawn since the certified data was last read