Heat Pump List

Tools

TWH24PR32DO

TWH24PR32DO is in the certified data.

Its certified full-speed heating output at 5°F is 18,000–19,000 Btu/h, 78–79% of its 47°F rating (tests at different compressor speeds), depending on the pairing.

Tosot · mini-split heat pump

All 294 certified Tosot models

TWH24PR32DO is in the certified data as of Sep 19, 2026.

2 certified pairings with 2 different figures. See all

Certified heating and cooling

Heating at 47°F

23,000

20,000 at 17°F

18,000 at 5°F

Btu/h, certified

1.80 COP at 5°F

Cooling at 95°F

21,000

Btu/h, certified

EER2 12.0 at 95°F

SEER2 23.5

Heating and cooling by outdoor temperature

Certified heating at 5, 17, and 47°F and cooling at 95°F for TWH24PR32DO, by outdoor temperature Heating: 18,000 Btu/h at 5°F, 20,000 Btu/h at 17°F, 23,000 Btu/h at 47°F. Cooling: 21,000 Btu/h at 95°F. The bars start at zero. Median of 1.5-ton mini-split models: 14,200 Btu/h at 5°F, 14,800 Btu/h at 17°F, 18,000 Btu/h at 47°F, 18,000 Btu/h at 95°F. 0 5,000 10,000 15,000 20,000 25,000 Btu/h 18,000 5°F 20,000 17°F 23,000 47°F 21,000 95°F Outdoor temperature (°F)
  • Heating output
  • Cooling output
  • Median of 1.5-ton mini-split models
  • Example heating load
  • Example cooling load
  • Frosting range, 17 to 45°F

This pairing delivers 23,000 Btu/h of heat at 47°F, 20,000 Btu/h at 17°F, and 18,000 Btu/h at 5°F, 78% of its 47°F rating. It delivers 21,000 Btu/h of cooling at 95°F. At 5°F that is 4,000 Btu/h above the example heating load of 14,000 Btu/h; at 95°F it is 14,000 Btu/h above the example cooling load of 7,000 Btu/h.

Each bar is a separate certified test, drawn at its outdoor temperature, starting at zero. The 47°F figure is at normal speed; the 17 and 5°F figures are at full speed. The short dark line on each bar is the median of 1.5-ton mini-split models, one value per model. The shaded 17 to 45°F band is the frosting range: the outdoor coil can frost, and the unit pauses to defrost.

The dashed lines are example loads for a typical area of about 600 sq ft where winters reach 5°F: heating runs from 14,000 Btu/h at 5°F to 0 at 65°F, and cooling runs from 0 at 65°F to 7,000 Btu/h at 95°F, at 1,000 sq ft per ton. A house in a hot climate or with large west-facing windows can need twice as much cooling. They are examples, not your building.

Calculate heating and cooling for your house

AHRI certificate 218442591 · listed by TOSOT · certified Jul 13, 2026 · 1 pairing carries these values

Rebates where you live

Meets the recorded equipment thresholds of 67 programs in 35 states, provinces, or territories:Alabama (1), Arizona (1), California (3), Colorado (2), Connecticut (3), Delaware (2), Idaho (2), Illinois (1), Kentucky (1), Maine (2), Maryland (3), Massachusetts (3), Michigan (2), Minnesota (2), Mississippi (2), Nevada (1), New Hampshire (3), New Jersey (7), New York (4), Oregon (2), Pennsylvania (4), Rhode Island (3), Tennessee (1), Texas (2), Utah (1), Vermont (3), Washington (2), Wisconsin (1), British Columbia (3), Manitoba (1), New Brunswick (1), Newfoundland and Labrador (1), Nova Scotia (2), Ontario (1), Yukon (2).

All 67 programs by state and province

Alabama

Arizona

California

Colorado

Connecticut

Delaware

Idaho

Illinois

Kentucky

Maine

Maryland

Massachusetts

Michigan

Minnesota

Mississippi

Nevada

New Hampshire

New Jersey

New York

Oregon

Pennsylvania

Rhode Island

Tennessee

Texas

Utah

Vermont

Washington

Wisconsin

British Columbia

Manitoba

New Brunswick

Newfoundland and Labrador

Nova Scotia

Ontario

Yukon

Threshold comparisons use the unit’s median certified figures across its pairings, not the pairing selected above. Meeting these thresholds means the equipment may qualify; it does not guarantee approval. Service-area, installation, and product-list requirements also apply.

All rebate programs and their published thresholds

Certified output and power use

Certified output for the selected pairingThe four bars share one scale. The comparison is with the median of 1.5-ton mini-split models. Heating tests run at 70°F indoors. The cooling test runs at 80°F indoors.
Outdoor temperature Certified outputBtu/h One scale vs class median COPat 5°F
5°Ffull speed 18,0005.28 kW +27% 1.80
17°Ffull speed 20,0005.86 kW +35% NR
47°Fnormal speed 23,0006.74 kW +28% NR
95°Fcooling, full load 21,0006.15 kW — NR

EER2 12.0 in that test. SEER2 23.5 over the modeled cooling season.

Power use at each temperature

Electrical input in the 5°F full-speed test
2.93kW
Electrical input in the 95°F cooling test
1.75kW
Seasonal average heating COP
2.64

These exclude backup resistance heat.

Updated Sep 19, 2026 · Methodology

How it compares with other 18,000 Btu heat pumps

1.5-ton mini-split models

This pairing at 5°F
18,000 Btu/h
This unit at 5°F median across its pairings
18,000 Btu/h
Median of 1.5-ton mini-split models at 5°F
14,200 Btu/h
Models in this group
1,110

This unit is above 71% of them, at number 319 of 1,110 by heat at 5°F. The middle half of the group runs 13,000 to 18,000 Btu/h.

This size class is defined by cooling capacity, so cooling is not compared here.

Among 18,000 Btu mini-split models, each by its median certified pairing, highest first: 5°F output as a share of its 47°F rating, 535th of 1,110; HSPF2, 734th of 1,114 (tied). Models without that figure are left out.

Similar ratings at 47°F

These mini-split models share the nominal cooling size. Comparisons use each model’s median certified figures across pairings.

  • TRUZA0181KA80: The same 23,000 Btu/h rating at 47°F; 6,200 Btu/h at 5°F (this model: 18,000).
  • PUZ-A18NKA7: The same 23,000 Btu/h rating at 47°F; 7,600 Btu/h at 5°F (this model: 18,000).
  • BXS4Z24UC0: The same 23,000 Btu/h rating at 47°F; HSPF2 9.0 (this model: 9.5).

Closest models by heat at 5°F

Every 18,000 Btu (1.5-ton) unit, ranked by cooling efficiency, then heating efficiency

Floor area at the cold test point

The median certified output of 18,000 Btu/h at 5°F matches the size calculator’s heating estimate for these floor areas, rounded to about 10 sq ft. Each range divides that output by the climate band’s heating rates.

Floor area by climate band and house condition
Climate bandHouse conditionBtu/h per sq ftApproximate sq ft
MildDrafty, little insulation24–42430–750
MildTypical16–26690–1,130
MildTight, well insulated10–181,000–1,800
ColdDrafty, little insulation28–52350–640
ColdTypical18–30600–1,000
ColdTight, well insulated12–22820–1,500
Very coldDrafty, little insulation32–58310–560
Very coldTypical22–38470–820
Very coldTight, well insulated16–28640–1,130

This is an estimate, not a house-specific load calculation. Output stays at the 5°F test point for every band; it does not predict output at the band’s winter design temperature.

Certified values for TWH24PR32DO

2 pairings · 2 AHRI certificates

This pairing is the one shown above. Under all pairings, a single figure means every pairing agrees and a range means the pairing decides.

Certified values for TWH24PR32DO
This pairingAll pairings
Heating
Heat output at 47°F normal speed 23,000 Btu/h 23,000–24,000 Btu/h
Heat output at 17°F full speed 20,000 Btu/h 20,000–21,800 Btu/h
Heat output at 5°F full speed 18,000 Btu/h 18,000–19,000 Btu/h
Heat output below 5°F NR NR
Cold output 5°F output as a % of the 47°F rating 78%
COP at 5°F full speed 1.80 1.80
HSPF2 Region IV 9.0 9.0–10.0
Cooling
Cooling capacity at 95°F full-load test 21,000 Btu/h 21,000–22,000 Btu/h
EER2 at 95°F 12.0 12.0–13.65
SEER2 cooling season 23.5 23.5–26.0
Cooling at other temperatures NR NR
Equipment and listing
Refrigerant R-32
Compressor Variable speed
Indoor unit TWH24R32A1DI 2 indoor units
FurnaceNo furnace None
Cold-climate designation EPA's designation, as published Yes On every pairing
ENERGY STAR Most Efficient EPA's designation, as published Yes On every pairing
Where it is sold US and Canada US and Canada
Model string as certified TWH24PR32DO

Across 2 certified pairings with 2 indoor models: heat at 5°F 18,000 Btu/h with TWH24R32A1DI to 19,000 Btu/h with TWH24PR32DI; HSPF2 9.0 with TWH24R32A1DI to 10.0 with TWH24PR32DI; SEER2 23.5 with TWH24R32A1DI to 26.0 with TWH24PR32DI. Endpoints name one indoor model where recorded; the furnace pairing can also change the figures.

Pairings, by indoor-unit class

2 indoor units · 2 certified pairings

One row per indoor unit certified with this outdoor unit.

Ductless indoor · 2 indoor units

  1. TWH24PR32DI TOSOT 19,000 Btu/hat 5°F, full speed

    1 pairing · 47°F 24,000 Btu/h · 95°F cooling 22,000 Btu/h · Cold output 79% · COP 1.80

  2. TWH24R32A1DI (the pairing on screen) TOSOT 18,000 Btu/hat 5°F, full speed

    1 pairing · 47°F 23,000 Btu/h · 95°F cooling 21,000 Btu/h · Cold output 78% · COP 1.80

Indoor units in the ductless indoor class
Indoor unit Brand At 5°FBtu/h · full speed At 47°FBtu/h · normal speed At 95°FBtu/h · cooling Cold output% of 47°F rating COP 5°Ffull speed Cold climate Pairings
TWH24PR32DI TOSOT 19,000 24,000 22,000 79% 1.80 Yes 1
TWH24R32A1DI (the pairing on screen) TOSOT 18,000 23,000 21,000 78% 1.80 Yes 1

The share is heat output at 5°F divided by the 47°F rating.

Showing 2 of 2 indoor units

Sold as, and units with identical certified values

Brands listing this model number

Model number as listed

Product history

  • TWH24PR32DO first appeared in the certified data between May 2025 and June 2025.

History and definitions

Other Clivia models by nominal cooling size: TAVCI7H4R09 (9,000 Btu), TWH09AUC25R32A1DO (9,000 Btu), TAVCI7H4R12 (12,000 Btu), TW12HP32A2AO (12,000 Btu), TW12HP32A2DO (12,000 Btu), TW12WH25A1DO (12,000 Btu), TWH12AUC25R32A1DO (12,000 Btu), TWH12PR32AO (12,000 Btu); more models from this brand.

Other Pular models by nominal cooling size: TWH09PR32DO (9,000 Btu), TW24HXP2A1DO (24,000 Btu), TWH24AG25A2DO (24,000 Btu), TWH24PD32AO (24,000 Btu).

History

First certified record
Most recent certified record
Measurements reported
Jul 13, 2026
Status
In the certified data

Field definitions

COP
Heat delivered for each unit of electricity used. A COP of 2.5 gives 2.5 times the heat of an electric baseboard heater.
HSPF2
Heating efficiency over a typical season. Higher uses less electricity.
SEER2
Cooling efficiency over a typical season. Higher uses less electricity.
EER2
Cooling output divided by electrical input in the 95°F full-load test, in Btu/h per watt.
Cold output
Heat output at 5°F as a percentage of the 47°F rating.
% of rating at 17°F
Heat output at 17°F as a percentage of the 47°F rating.

NR not in the certified dataNC not cold-climate certifiedSP single pairing onlyVP varies by pairing; see the pairings tableWD withdrawn since the certified data was last read

Cite or print this page

Heat Pump List, “TWH24PR32DO — certified heat output”. Certified figures dated , checked daily.
https://heatpumplist.com/model/twh24pr32do