Heat Pump List

Tools

37MARAQ30AA3

37MARAQ30AA3 is in the certified data.

Its certified full-speed heating output at 5°F is 20,000–20,400 Btu/h, 67–68% of its 47°F rating (tests at different compressor speeds), depending on the pairing.

Bryant, Carrier + 3 more · mini-split heat pump

All 205 certified Bryant models · All 187 certified Carrier models · All 359 certified Midea models · All 107 certified Payne models · All 123 certified WeatherMaker models

37MARAQ30AA3 is in the certified data as of Sep 19, 2026.

12 certified pairings with 2 different figures. See all

Certified heating and cooling

Heating at 47°F

30,000

20,400 at 17°F

20,000 at 5°F

Btu/h, certified

2.03 COP at 5°F

Cooling at 95°F

30,000

Btu/h, certified

EER2 12.0 at 95°F

SEER2 20.5

Heating and cooling by outdoor temperature

Certified heating at 5, 17, and 47°F and cooling at 95°F for 37MARAQ30AA3, by outdoor temperature Heating: 20,000 Btu/h at 5°F, 20,400 Btu/h at 17°F, 30,000 Btu/h at 47°F. Cooling: 30,000 Btu/h at 95°F. The bars start at zero. Median of 2.5-ton mini-split models: 25,000 Btu/h at 5°F, 25,600 Btu/h at 17°F, 30,000 Btu/h at 47°F, 30,000 Btu/h at 95°F. 0 10,000 20,000 30,000 Btu/h 20,000 5°F 20,400 17°F 30,000 47°F 30,000 95°F Outdoor temperature (°F)
  • Heating output
  • Cooling output
  • Median of 2.5-ton mini-split models
  • Example heating load
  • Example cooling load
  • Frosting range, 17 to 45°F

This pairing delivers 30,000 Btu/h of heat at 47°F, 20,400 Btu/h at 17°F, and 20,000 Btu/h at 5°F, 67% of its 47°F rating. It delivers 30,000 Btu/h of cooling at 95°F. At 5°F that is 5,000 Btu/h short of the example heating load of 25,000 Btu/h; at 95°F it is 17,500 Btu/h above the example cooling load of 12,500 Btu/h.

Each bar is a separate certified test, drawn at its outdoor temperature, starting at zero. The 47°F figure is at normal speed; the 17 and 5°F figures are at full speed. The short dark line on each bar is the median of 2.5-ton mini-split models, one value per model. The shaded 17 to 45°F band is the frosting range: the outdoor coil can frost, and the unit pauses to defrost.

The dashed lines are example loads for a typical area of about 1,050 sq ft where winters reach 5°F: heating runs from 25,000 Btu/h at 5°F to 0 at 65°F, and cooling runs from 0 at 65°F to 12,500 Btu/h at 95°F, at 1,000 sq ft per ton. A house in a hot climate or with large west-facing windows can need twice as much cooling. They are examples, not your building.

Calculate heating and cooling for your house

AHRI certificate 215413145 · listed by Carrier · certified Mar 4, 2025 · 7 pairings share these values

Rebates where you live

Meets the recorded equipment thresholds of 49 programs in 27 states, provinces, or territories:Alabama (1), Arizona (1), California (3), Colorado (1), Delaware (2), Idaho (2), Illinois (1), Kentucky (1), Maine (2), Maryland (3), Michigan (2), Minnesota (1), Mississippi (2), Nevada (1), New Hampshire (1), New Jersey (7), New York (4), Oregon (2), Pennsylvania (4), Tennessee (1), Texas (2), Utah (1), Vermont (3), Washington (1), Wisconsin (1), British Columbia (3), Newfoundland and Labrador (1).

All 49 programs by state and province

Alabama

Arizona

California

Colorado

Delaware

Idaho

Illinois

Kentucky

Maine

Maryland

Michigan

Minnesota

Mississippi

Nevada

New Hampshire

New Jersey

New York

Oregon

Pennsylvania

Tennessee

Texas

Utah

Vermont

Washington

Wisconsin

British Columbia

Newfoundland and Labrador

Threshold comparisons use the unit’s median certified figures across its pairings, not the pairing selected above. Meeting these thresholds means the equipment may qualify; it does not guarantee approval. Service-area, installation, and product-list requirements also apply.

All rebate programs and their published thresholds

Certified output and power use

Certified output for the selected pairingThe four bars share one scale. The comparison is with the median of 2.5-ton mini-split models. Heating tests run at 70°F indoors. The cooling test runs at 80°F indoors.
Outdoor temperature Certified outputBtu/h One scale vs class median COPat 5°F
5°Ffull speed 20,0005.86 kW −20% 2.03
17°Ffull speed 20,4005.98 kW −20% NR
47°Fnormal speed 30,0008.79 kW 0% NR
95°Fcooling, full load 30,0008.79 kW — NR

EER2 12.0 in that test. SEER2 20.5 over the modeled cooling season.

Power use at each temperature

Electrical input in the 5°F full-speed test
2.89kW
Electrical input in the 95°F cooling test
2.50kW
Seasonal average heating COP
2.78

These exclude backup resistance heat.

Updated Sep 19, 2026 · Methodology

How it compares with other 30,000 Btu heat pumps

2.5-ton mini-split models

This pairing at 5°F
20,000 Btu/h
This unit at 5°F median across its pairings
20,000 Btu/h
Median of 2.5-ton mini-split models at 5°F
25,000 Btu/h
Models in this group
405

This unit is above 21% of them, at number 318 of 405 by heat at 5°F. The middle half of the group runs 20,000 to 27,000 Btu/h.

This size class is defined by cooling capacity, so cooling is not compared here.

Among 30,000 Btu mini-split models, each by its median certified pairing, highest first: 5°F output as a share of its 47°F rating, 330th of 405 (tied); HSPF2, 188th of 405 (tied). Models without that figure are left out.

Similar ratings at 47°F

These mini-split models share the nominal cooling size. Comparisons use each model’s median certified figures across pairings.

  • AOUH30LUAH1: The same 30,000 Btu/h rating at 47°F; 33,000 Btu/h at 5°F (this model: 20,000).
  • AOU30RLXEH: The same 30,000 Btu/h rating at 47°F; 30,400 Btu/h at 5°F (this model: 20,000).
  • 37VMB030HDS3-1: The same 30,000 Btu/h rating at 47°F; 30,000 Btu/h at 5°F (this model: 20,000).

Closest models by heat at 5°F

Every 30,000 Btu (2.5-ton) unit, ranked by cooling efficiency, then heating efficiency

Floor area at the cold test point

The median certified output of 20,000 Btu/h at 5°F matches the size calculator’s heating estimate for these floor areas, rounded to about 10 sq ft. Each range divides that output by the climate band’s heating rates.

Floor area by climate band and house condition
Climate bandHouse conditionBtu/h per sq ftApproximate sq ft
MildDrafty, little insulation24–42480–830
MildTypical16–26770–1,250
MildTight, well insulated10–181,110–2,000
ColdDrafty, little insulation28–52380–710
ColdTypical18–30670–1,110
ColdTight, well insulated12–22910–1,670
Very coldDrafty, little insulation32–58340–630
Very coldTypical22–38530–910
Very coldTight, well insulated16–28710–1,250

This is an estimate, not a house-specific load calculation. Output stays at the 5°F test point for every band; it does not predict output at the band’s winter design temperature.

Certified values for 37MARAQ30AA3

12 pairings · 12 AHRI certificates

This pairing is the one shown above. Under all pairings, a single figure means every pairing agrees and a range means the pairing decides.

Certified values for 37MARAQ30AA3
This pairingAll pairings
Heating
Heat output at 47°F normal speed 30,000 Btu/h 30,000 Btu/h
Heat output at 17°F full speed 20,400 Btu/h 19,400–20,400 Btu/h
Heat output at 5°F full speed 20,000 Btu/h 20,000–20,400 Btu/h
Heat output below 5°F NR NR
Cold output 5°F output as a % of the 47°F rating 67%
COP at 5°F full speed 2.03 2.03–2.10
HSPF2 Region IV 9.5 8.8–9.5
Cooling
Cooling capacity at 95°F full-load test 30,000 Btu/h 30,000 Btu/h
EER2 at 95°F 12.0 11.0–12.0
SEER2 cooling season 20.5 17.0–20.5
Cooling at other temperatures NR NR
Equipment and listing
Refrigerant R-454B
Compressor Variable speed
Indoor unit 45MAHAQ30XA3 4 indoor units
FurnaceNo furnace None
Cold-climate designation EPA's designation, as published NC NC
ENERGY STAR Most Efficient EPA's designation, as published Yes On some pairings
Where it is sold US and Canada US and Canada
Model string as certified 37MARAQ30AA3

Across 12 certified pairings with 4 indoor models: heat at 5°F 20,000 Btu/h with 45MAHAQ30XA3 to 20,400 Btu/h with 45MBAAQ30XB3; HSPF2 8.8 with 45MBAAQ30XB3 to 9.5 with 45MAHAQ30XA3; SEER2 17.0 with 45MBAAQ30XB3 to 20.5 with 45MAHAQ30XA3. Endpoints name one indoor model where recorded; the furnace pairing can also change the figures.

Pairings, by indoor-unit class

4 indoor units · 12 certified pairings

One row per indoor unit certified with this outdoor unit.

Air handler · 1 indoor unit

  1. 45MBAAQ30XB3 brand not stated 20,400 Btu/hat 5°F, full speed

    5 pairings · 47°F 30,000 Btu/h · 95°F cooling 30,000 Btu/h · Cold output 68% · COP 2.10

Indoor units in the air handler class
Indoor unit Brand At 5°FBtu/h · full speed At 47°FBtu/h · normal speed At 95°FBtu/h · cooling Cold output% of 47°F rating COP 5°Ffull speed Cold climate Pairings
45MBAAQ30XB3 — 20,400 30,000 30,000 68% 2.10 NC 5

Ductless indoor · 3 indoor units

  1. D5MAHAQ30XA3 BRYANT 20,000 Btu/hat 5°F, full speed

    5 pairings · 47°F 30,000 Btu/h · 95°F cooling 30,000 Btu/h · Cold output 67% · COP 2.03

  2. 45MAHAQ30XA3 (the pairing on screen) CARRIER 20,000 Btu/hat 5°F, full speed

    1 pairing · 47°F 30,000 Btu/h · 95°F cooling 30,000 Btu/h · Cold output 67% · COP 2.03

  3. 615AHAQ30XA3 BRYANT 20,000 Btu/hat 5°F, full speed

    1 pairing · 47°F 30,000 Btu/h · 95°F cooling 30,000 Btu/h · Cold output 67% · COP 2.03

Indoor units in the ductless indoor class
Indoor unit Brand At 5°FBtu/h · full speed At 47°FBtu/h · normal speed At 95°FBtu/h · cooling Cold output% of 47°F rating COP 5°Ffull speed Cold climate Pairings
D5MAHAQ30XA3 BRYANT 20,000 30,000 30,000 67% 2.03 NC 5
45MAHAQ30XA3 (the pairing on screen) CARRIER 20,000 30,000 30,000 67% 2.03 NC 1
615AHAQ30XA3 BRYANT 20,000 30,000 30,000 67% 2.03 NC 1

The share is heat output at 5°F divided by the 47°F rating.

Showing 4 of 4 indoor units

Sold as, and units with identical certified values

History and definitions

Other 37M Series models by nominal cooling size: 37MAHAQ06AA3 (6,000 Btu), 37MPRAQ06AA3 (6,000 Btu), 37MAHAQ09AA3 (9,000 Btu), 37MARAQ09AA3 (9,000 Btu), 37MPRAQ09AA3 (9,000 Btu), 37MAHAQ12AA3 (12,000 Btu), 37MARAQ12AA1 (12,000 Btu), 37MARAQ12AA3 (12,000 Btu); more models from this brand.

Other 45M Series models by nominal cooling size: 37MAHAQ06AA3 (6,000 Btu), 37MAHAQ09AA3 (9,000 Btu), 37MARAQ09AA3 (9,000 Btu), 37MHRAQ09AA1 (9,000 Btu), 37MHRAQ09AA3 (9,000 Btu), 37MAHAQ12AA3 (12,000 Btu), 37MARAQ12AA3 (12,000 Btu), 37MAHAQ18AA3 (18,000 Btu); more models from this brand.

Other 615 Series models by nominal cooling size: 37MAHAQ06AA3 (6,000 Btu), 37MPRAQ06AA3 (6,000 Btu), 37MAHAQ09AA3 (9,000 Btu), 37MARAQ09AA3 (9,000 Btu), 37MPRAQ09AA3 (9,000 Btu), 37MAHAQ12AA3 (12,000 Btu), 37MARAQ12AA1 (12,000 Btu), 37MARAQ12AA3 (12,000 Btu); more models from this brand.

History

First certified record
Most recent certified record
Measurements reported
Mar 4, 2025
Status
In the certified data

Field definitions

COP
Heat delivered for each unit of electricity used. A COP of 2.5 gives 2.5 times the heat of an electric baseboard heater.
HSPF2
Heating efficiency over a typical season. Higher uses less electricity.
SEER2
Cooling efficiency over a typical season. Higher uses less electricity.
EER2
Cooling output divided by electrical input in the 95°F full-load test, in Btu/h per watt.
Cold output
Heat output at 5°F as a percentage of the 47°F rating.
% of rating at 17°F
Heat output at 17°F as a percentage of the 47°F rating.

NR not in the certified dataNC not cold-climate certifiedSP single pairing onlyVP varies by pairing; see the pairings tableWD withdrawn since the certified data was last read

Cite or print this page

Heat Pump List, “37MARAQ30AA3 — certified heat output”. Certified figures dated , checked daily.
https://heatpumplist.com/model/37maraq30aa3