AS-12UW3SXADL
AS-12UW3SXADL is in the certified data.
Its certified full-speed heating output at 5°F is 8,400 Btu/h2.46 kW, 70% of its 47°F rating (tests at different compressor speeds) in its certified pairing.
Hisense · mini-split heat pump
AS-12UW3SXADL is in the certified data as of Sep 19, 2026.
- 12,000 Btu (1-ton)
- Mini-split
- Variable speed
- Canada
Certified heating and cooling
Heating at 47°F
12,0003.52NR
No 47°F rating for this pairing.
7,0002.05NR at 17°F
8,4002.46NR at 5°F
Btu/hkW, certified
1.75NR COP at 5°F
Heating and cooling by outdoor temperature
This pairing delivers 12,000 Btu/h3.52 kW of heat at 47°F, 7,000 Btu/h2.05 kW at 17°F, and 8,400 Btu/h2.46 kW at 5°F, 70% of its 47°F rating. It delivers 12,000 Btu/h3.52 kW of cooling at 95°F. At 5°F that is 600 Btu/h0.18 kW short of the example heating load of 9,000 Btu/h2.64 kW; at 95°F it is 7,000 Btu/h2.05 kW above the example cooling load of 5,000 Btu/h1.47 kW.
Each bar is a separate certified test, drawn at its outdoor temperature, starting at zero. The 47°F figure is at normal speed; the 17 and 5°F figures are at full speed. The short dark line on each bar is the median of 1-ton mini-split models, one value per model. The shaded 17 to 45°F band is the frosting range: the outdoor coil can frost, and the unit pauses to defrost.
The dashed lines are example loads for a typical area of about 400 sq ft where winters reach 5°F: heating runs from 9,000 Btu/h2.64 kW at 5°F to 0 at 65°F, and cooling runs from 0 at 65°F to 5,000 Btu/h1.47 kW at 95°F, at 1,000 sq ft per ton. A house in a hot climate or with large west-facing windows can need twice as much cooling. They are examples, not your building.
AHRI certificate 206347232 · listed by Hisense · certified Jun 9, 2026 · 1 pairing carries these values
Rebates where you live
A utility program is for that utility's customers.
Choose location
Threshold comparisons use the unit’s certified figures across its pairings. Programs also set service-area, installation, and product-list requirements.
Certified output and power use
| Outdoor temperature | Certified outputBtu/h | One scale | vs class median | COPat 5°F |
|---|---|---|---|---|
| 5°Ffull speed | 8,4002.46 kW | −9% | 1.75 | |
| 17°Ffull speed | 7,0002.05 kW | −29% | NR | |
| 47°Fnormal speed | 12,0003.52 kW | 0% | NR | |
| 95°Fcooling, full load | 12,0003.52 kW | — | NR |
EER2 15.4 in that test. SEER2 23.5 over the modeled cooling season.
Power use at each temperature
- Electrical input in the 5°F full-speed test
- 1.41kW
- Electrical input in the 95°F cooling test
- 0.78kW
- Seasonal average heating COP
- 2.74
These exclude backup resistance heat.
How it compares with other 12,000 Btu heat pumps
1-ton mini-split models
- This pairing at 5°F
- 8,400 Btu/h2.46 kWNR
- This unit at 5°F median across its pairings
- 8,400 Btu/h2.46 kW
- Median of 1-ton mini-split models at 5°F
- 9,200 Btu/h2.70 kW
- Models in this group
- 888
This unit is above 13% of them, at number 769 of 888 by heat at 5°F. The middle half of the group runs 8,400 to 11,300 Btu/h.
Closest models by heat at 5°F
- MOS12H2XE5AInnovair · 8,500 Btu/h
- 454-12-O-DADuctlessAire · 8,400 Btu/h
- AS-12UR3SXA00Hisense · 8,400 Btu/h
- ASG24-12H220V1BApooDr and AproDr · 8,400 Btu/h
- AST-12UW3SXE01Hisense · 8,400 Btu/h
- BMS500-AAS012-1CSXRDBosch · 8,400 Btu/h
Every 12,000 Btu (1-ton) unit, ranked by cooling efficiency, then heating efficiency
Certified values for AS-12UW3SXADL
1 pairing · 1 AHRI certificate
This pairing is the one shown above. Under all pairings, a single figure means every pairing agrees and a range means the pairing decides.
| This pairing | All pairings | |
|---|---|---|
| Heating | ||
| Heat output at 47°F normal speed | 12,000 Btu/h3.52 kWNR | 12,000 Btu/h3.52 kW |
| Heat output at 17°F full speed | 7,000 Btu/h2.05 kWNR | 7,000 Btu/h2.05 kW |
| Heat output at 5°F full speed | 8,400 Btu/h2.46 kWNR | 8,400 Btu/h2.46 kW |
| Heat output below 5°F | NR | NR |
| Cold output 5°F output as a % of the 47°F rating | 70%NR | |
| COP at 5°F full speed | 1.75NR | 1.75 |
| HSPF2 Region IV | 9.4NR | 9.4 |
| Cooling | ||
| Cooling capacity at 95°F full-load test | 12,000 Btu/h3.52 kWNR | 12,000 Btu/h3.52 kW |
| EER2 at 95°F | 15.4NR | 15.4 |
| SEER2 cooling season | 23.5NR | 23.5 |
| Cooling at other temperatures | NR | NR |
| Equipment and listing | ||
| Refrigerant | R-410A | |
| Compressor | Variable speed | |
| Indoor unit | AS-12UW3SXADL | 1 indoor unit |
| Furnace | No furnace | None |
| Cold-climate designation EPA's designation, as published | Yes | On every pairing |
| ENERGY STAR Most Efficient EPA's designation, as published | Yes | On every pairing |
| Where it is sold | Canada | Canada |
| Model string as certified | AS-12UW3SXADL | |
Pairings, by indoor-unit class
1 indoor unit · 1 certified pairing
One row per indoor unit certified with this outdoor unit.
Ductless indoor · 1 indoor unit
-
AS-12UW3SXADL (the pairing on screen) HISENSE 8,400 Btu/h2.46 kWat 5°F, full speed
| Indoor unit | Brand | At 5°FBtu/hkW · full speed | At 47°FBtu/hkW · normal speed | At 95°FBtu/hkW · cooling | Cold output% of 47°F rating | COP 5°Ffull speed | Cold climate | Pairings |
|---|---|---|---|---|---|---|---|---|
| AS-12UW3SXADL (the pairing on screen) | HISENSE | 8,4002.46 | 12,0003.52 | 12,0003.52 | 70% | 1.75 | Yes | 1 |
Sold as, and units with identical certified values
Variants of the same model number
2 units in this group. Basis: identical certified values in the certified data. This grouping is our inference, not a field in the certified data.
1 of 2 shown.
Other model numbers with identical certified values
2 units share this record. Basis: identical certified values in the certified data. This grouping is our inference, not a field in the certified data.
1 of 2 shown.
What affects the price
We don't have prices. These things drive the cost.
- The size of the unit, and the indoor equipment on the same certificate.
- Whether existing ductwork is reused, altered, or replaced.
- The electrical work: a circuit, a disconnect, and sometimes a panel change.
- Refrigerant line length and how the outdoor unit is mounted.
- Permits and inspection, which vary by municipality.
- Removing and disposing of the old equipment.
- Local labor rates and how busy the season is.
- Rebates and tax credits, which change and have deadlines.
History and definitions
History
- First certified record
- Most recent certified record
- Measurements reported
- Jun 9, 2026
- Status
- In the certified data
Field definitions
- COP
- Heat delivered for each unit of electricity used. A COP of 2.5 gives 2.5 times the heat of an electric baseboard heater.
- HSPF2
- Heating efficiency over a typical season. Higher uses less electricity.
- SEER2
- Cooling efficiency over a typical season. Higher uses less electricity.
- EER2
- Cooling output divided by electrical input in the 95°F full-load test, in Btu/h per watt.
- Cold output
- Heat output at 5°F as a percentage of the 47°F rating.
- % of rating at 17°F
- Heat output at 17°F as a percentage of the 47°F rating.
NR not in the certified dataNC not cold-climate certifiedSP single pairing onlyVP varies by pairing; see the pairings tableWD withdrawn since the certified data was last read