Heat Pump List

Tools

GWHD(30)ND6MO

Gree · mini-split heat pump

All 252 certified Gree models

GWHD(30)ND6MO is in the certified data as of Sep 19, 2026. GWHD(30)ND6MO changed its certified HSPF2 on AHRI certificate 214931594 from 8.0 to 8.1 in the certified data between September 2024 and November 2024.

3 certified pairings with 3 different figures. See all

Certified heating and cooling

Heating at 47°F

30,000

27,600 at 17°F

26,400 at 5°F

Btu/h, certified

1.81 COP at 5°F

Cooling at 95°F

28,400

Btu/h, certified

EER2 12.2 at 95°F

SEER2 19.0

Heating and cooling by outdoor temperature

Certified heating at 5, 17, and 47°F and cooling at 95°F for GWHD(30)ND6MO, by outdoor temperature Heating: 26,400 Btu/h at 5°F, 27,600 Btu/h at 17°F, 30,000 Btu/h at 47°F. Cooling: 28,400 Btu/h at 95°F. The bars start at zero. Median of 2.5-ton mini-split models: 25,000 Btu/h at 5°F, 25,600 Btu/h at 17°F, 30,000 Btu/h at 47°F, 30,000 Btu/h at 95°F. 0 10,000 20,000 30,000 Btu/h 26,400 5°F 27,600 17°F 30,000 47°F 28,400 95°F Outdoor temperature (°F)
  • Heating output
  • Cooling output
  • Median of 2.5-ton mini-split models
  • Example heating load
  • Example cooling load
  • Frosting range, 17 to 45°F

This pairing delivers 30,000 Btu/h of heat at 47°F, 27,600 Btu/h at 17°F, and 26,400 Btu/h at 5°F, 88% of its 47°F rating. It delivers 28,400 Btu/h of cooling at 95°F. At 5°F that is 1,400 Btu/h above the example heating load of 25,000 Btu/h; at 95°F it is 15,900 Btu/h above the example cooling load of 12,500 Btu/h.

Each bar is a separate certified test, drawn at its outdoor temperature, starting at zero. The 47°F figure is at normal speed; the 17 and 5°F figures are at full speed. The short dark line on each bar is the median of 2.5-ton mini-split models, one value per model. The shaded 17 to 45°F band is the frosting range: the outdoor coil can frost, and the unit pauses to defrost.

The dashed lines are example loads for a typical area of about 1,050 sq ft where winters reach 5°F: heating runs from 25,000 Btu/h at 5°F to 0 at 65°F, and cooling runs from 0 at 65°F to 12,500 Btu/h at 95°F, at 1,000 sq ft per ton. A house in a hot climate or with large west-facing windows can need twice as much cooling. They are examples, not your building.

Calculate heating and cooling for your house

AHRI certificate 214931598 · listed by GREE · certified Apr 21, 2026 · 1 pairing carries these values

Certified output and power use

Certified output for the selected pairingThe four bars share one scale. The comparison is with the median of 2.5-ton mini-split models. Heating tests run at 70°F indoors. The cooling test runs at 80°F indoors.
Outdoor temperature Certified outputBtu/h One scale vs class median COPat 5°F
5°Ffull speed 26,4007.74 kW +6% 1.81
17°Ffull speed 27,6008.09 kW +8% NR
47°Fnormal speed 30,0008.79 kW 0% NR
95°Fcooling, full load 28,4008.32 kW — NR

EER2 12.2 in that test. SEER2 19.0 over the modeled cooling season.

Power use at each temperature

Electrical input in the 5°F full-speed test
4.27kW
Electrical input in the 95°F cooling test
2.33kW
Seasonal average heating COP
2.64

These exclude backup resistance heat.

Updated Sep 19, 2026 · Methodology

How it compares with other 30,000 Btu heat pumps

2.5-ton mini-split models

This pairing at 5°F
26,400 Btu/h
This unit at 5°F median across its pairings
26,400 Btu/h
Median of 2.5-ton mini-split models at 5°F
25,000 Btu/h
Models in this group
405

This unit is above 57% of them, at number 173 of 405 by heat at 5°F. The middle half of the group runs 20,000 to 27,000 Btu/h.

This size class is defined by cooling capacity, so cooling is not compared here.

Among 30,000 Btu mini-split models, each by its median certified pairing, highest first: 5°F output as a share of its 47°F rating, 180th of 405 (tied); HSPF2, 275th of 405 (tied). Models without that figure are left out.

Similar ratings at 47°F

These mini-split models share the nominal cooling size. Comparisons use each model’s median certified figures across pairings.

  • AOD30-30HFN1-MS0W: The same 30,000 Btu/h rating at 47°F; 17,500 Btu/h at 5°F (this model: 26,400).
  • ADSZ130DA: The same 30,000 Btu/h rating at 47°F; 18,000 Btu/h at 5°F (this model: 26,400).
  • MOD-30HFN1CA: The same 30,000 Btu/h rating at 47°F; 18,400 Btu/h at 5°F (this model: 26,400).

Closest models by heat at 5°F

Every 30,000 Btu (2.5-ton) unit, ranked by cooling efficiency, then heating efficiency

Floor area at the cold test point

The median certified output of 26,400 Btu/h at 5°F matches the size calculator’s heating estimate for these floor areas, rounded to about 10 sq ft. Each range divides that output by the climate band’s heating rates.

Floor area by climate band and house condition
Climate bandHouse conditionBtu/h per sq ftApproximate sq ft
MildDrafty, little insulation24–42630–1,100
MildTypical16–261,020–1,650
MildTight, well insulated10–181,470–2,640
ColdDrafty, little insulation28–52510–940
ColdTypical18–30880–1,470
ColdTight, well insulated12–221,200–2,200
Very coldDrafty, little insulation32–58460–830
Very coldTypical22–38690–1,200
Very coldTight, well insulated16–28940–1,650

This is an estimate, not a house-specific load calculation. Output stays at the 5°F test point for every band; it does not predict output at the band’s winter design temperature.

Certified values for GWHD(30)ND6MO

3 pairings · 3 AHRI certificates

This pairing is the one shown above. Under all pairings, a single figure means every pairing agrees and a range means the pairing decides.

Certified values for GWHD(30)ND6MO
This pairingAll pairings
Heating
Heat output at 47°F normal speed 30,000 Btu/h 30,000 Btu/h
Heat output at 17°F full speed 27,600 Btu/h 27,200–28,000 Btu/h
Heat output at 5°F full speed 26,400 Btu/h 26,000–27,000 Btu/h
Heat output below 5°F NR NR
Cold output 5°F output as a % of the 47°F rating 88%
COP at 5°F full speed 1.81 1.81–2.07
HSPF2 Region IV 9.0 8.1–10.0
Cooling
Cooling capacity at 95°F full-load test 28,400 Btu/h 28,400 Btu/h
EER2 at 95°F 12.2 12.0–13.6
SEER2 cooling season 19.0 18.0–21.0
Cooling at other temperatures NR NR
Equipment and listing
Refrigerant R-32
Compressor Variable speed
Indoor unit None listed None
FurnaceNo furnace None
Cold-climate designation EPA's designation, as published Yes On every pairing
ENERGY STAR Most Efficient EPA's designation, as published Yes On some pairings
Where it is sold US and Canada US and Canada
Model string as certified GWHD(30)ND6MO

Pairings, by indoor-unit class

3 certified pairings

One row per indoor unit certified with this outdoor unit.

Ductless indoor

  1. None listed (the pairing on screen) GREE 26,400 Btu/hat 5°F, full speed

    3 pairings · 47°F 30,000 Btu/h · 95°F cooling 28,400 Btu/h · Cold output 88% · COP 1.88

Indoor units in the ductless indoor class
Indoor unit Brand At 5°FBtu/h · full speed At 47°FBtu/h · normal speed At 95°FBtu/h · cooling Cold output% of 47°F rating COP 5°Ffull speed Cold climate Pairings
None listed (the pairing on screen) GREE 26,400 30,000 28,400 88% 1.88 Yes 3

The share is heat output at 5°F divided by the 47°F rating.

Sold as, and units with identical certified values

Brands listing this model number

Model number as listed

Variants of the same model number

20 units in this group. Basis: identical certified values in the certified data. This grouping is our inference, not a field in the certified data.

19 of 20 shown.

Other model numbers with identical certified values

19 units share this record. Basis: identical certified values in the certified data. This grouping is our inference, not a field in the certified data.

18 of 19 shown.

Product history

  • GWHD(30)ND6MO changed its certified HSPF2 on AHRI certificate 214931594 from 8.0 to 8.1 in the certified data between September 2024 and November 2024.
  • GWHD(30)ND6MO was in the certified data by September 2024.

History and definitions

Other M-Series models by nominal cooling size: GS2M18HP230V1MO (18,000 Btu), GWHD(18)ND3NO (18,000 Btu), MUL19HP230V1R32AO (18,000 Btu), GS3M24HP230V1MO (24,000 Btu), GWHD(24)ND3NO (24,000 Btu), GS4M30HP230V1MO (30,000 Btu), GWHD(30)ND3NO (30,000 Btu), GS4M36HP230V1MO (36,000 Btu); more models from this brand.

History

First certified record
Most recent certified record
Measurements reported
Apr 21, 2026
Status
In the certified data

Field definitions

COP
Heat delivered for each unit of electricity used. A COP of 2.5 gives 2.5 times the heat of an electric baseboard heater.
HSPF2
Heating efficiency over a typical season. Higher uses less electricity.
SEER2
Cooling efficiency over a typical season. Higher uses less electricity.
EER2
Cooling output divided by electrical input in the 95°F full-load test, in Btu/h per watt.
Cold output
Heat output at 5°F as a percentage of the 47°F rating.
% of rating at 17°F
Heat output at 17°F as a percentage of the 47°F rating.

NR not in the certified dataNC not cold-climate certifiedSP single pairing onlyVP varies by pairing; see the pairings tableWD withdrawn since the certified data was last read

Cite or print this page

Heat Pump List, “GWHD(30)ND6MO — certified heat output”. Certified figures dated , checked daily.
https://heatpumplist.com/model/gs4m30hp230v1mo