Heat Pump List

Tools

HVH837GKA2

HVH837GKA2 is in the certified data.

Its certified full-speed heating output at 5°F is 24,000–24,400 Btu/h, 51–53% of its 47°F rating, depending on the pairing.

ACiQ, Airquest + 2 more · central heat pump

All 133 certified ACiQ models · All 175 certified Airquest models · All 175 certified Arcoaire models · All 176 certified Heil models

HVH837GKA2 is in the certified data as of Sep 19, 2026.

209 certified pairings with 40 different figures. See all

Certified heating and cooling

Heating at 47°F

46,500

30,400 at 17°F

24,200 at 5°F

Btu/h, certified

1.96 COP at 5°F

Cooling at 95°F

32,600

Btu/h, certified

EER2 11.7 at 95°F

SEER2 17.5

Heating and cooling by outdoor temperature

Certified heating at 5, 17, and 47°F and cooling at 95°F for HVH837GKA2, by outdoor temperature Heating: 24,200 Btu/h at 5°F, 30,400 Btu/h at 17°F, 46,500 Btu/h at 47°F. Cooling: 32,600 Btu/h at 95°F. The bars start at zero. Median of 2.5-ton central models: 22,400 Btu/h at 5°F, 20,600 Btu/h at 17°F, 30,000 Btu/h at 47°F, 30,000 Btu/h at 95°F. 0 10,000 20,000 30,000 40,000 50,000 Btu/h 24,200 5°F 30,400 17°F 46,500 47°F 32,600 95°F Outdoor temperature (°F)
  • Heating output
  • Cooling output
  • Median of 2.5-ton central models
  • Example heating load
  • Example cooling load
  • Frosting range, 17 to 45°F

This pairing delivers 46,500 Btu/h of heat at 47°F, 30,400 Btu/h at 17°F, and 24,200 Btu/h at 5°F, 52% of its 47°F rating. It delivers 32,600 Btu/h of cooling at 95°F. At 5°F that is 1,700 Btu/h above the example heating load of 22,500 Btu/h; at 95°F it is 21,100 Btu/h above the example cooling load of 11,500 Btu/h.

Each bar is a separate certified test, drawn at its outdoor temperature, starting at zero. The 47°F figure is at high stage; the 17 and 5°F figures are at full speed. The short dark line on each bar is the median of 2.5-ton central models, one value per model. The shaded 17 to 45°F band is the frosting range: the outdoor coil can frost, and the unit pauses to defrost.

The dashed lines are example loads for a typical area of about 950 sq ft where winters reach 5°F: heating runs from 22,500 Btu/h at 5°F to 0 at 65°F, and cooling runs from 0 at 65°F to 11,500 Btu/h at 95°F, at 1,000 sq ft per ton. A house in a hot climate or with large west-facing windows can need twice as much cooling. They are examples, not your building.

Calculate heating and cooling for your house

AHRI certificate 210460968 · listed by Heil · certified May 15, 2025 · 12 pairings share these values

Rebates where you live

Meets the recorded equipment thresholds of 33 programs in 22 states, provinces, or territories:California (1), Colorado (1), Delaware (1), Idaho (2), Illinois (1), Kansas (1), Maryland (3), Michigan (2), Minnesota (2), Mississippi (1), Nevada (1), New Hampshire (1), New Jersey (4), North Carolina (1), Oregon (2), Pennsylvania (3), South Carolina (1), Texas (3), Utah (1), Washington (2), Wisconsin (1), Newfoundland and Labrador (1).

All 33 programs by state and province

California

Colorado

Delaware

Idaho

Illinois

Kansas

Maryland

Michigan

Minnesota

Mississippi

Nevada

New Hampshire

New Jersey

North Carolina

Oregon

Pennsylvania

South Carolina

Texas

Utah

Washington

Wisconsin

Newfoundland and Labrador

Threshold comparisons use the unit’s median certified figures across its pairings, not the pairing selected above. Meeting these thresholds means the equipment may qualify; it does not guarantee approval. Service-area, installation, and product-list requirements also apply.

All rebate programs and their published thresholds

Certified output and power use

Certified output for the selected pairingThe four bars share one scale. The comparison is with the median of 2.5-ton central models. Heating tests run at 70°F indoors. The cooling test runs at 80°F indoors.
Outdoor temperature Certified outputBtu/h One scale vs class median COPat 5°F
5°Fone compressor speed 24,2007.09 kW +8% 1.96
17°Fone compressor speed 30,4008.91 kW +48% NR
47°Fone compressor speed 46,50013.63 kW +55% NR
95°Fcooling, full load 32,6009.55 kW — NR

EER2 11.7 in that test. SEER2 17.5 over the modeled cooling season.

Power use at each temperature

Electrical input in the 5°F full-speed test
3.62kW
Electrical input in the 95°F cooling test
2.79kW
Seasonal average heating COP
2.37

These exclude backup resistance heat.

Updated Sep 19, 2026 · Methodology

How it compares with other 30,000 Btu heat pumps

2.5-ton central models

This pairing at 5°F
24,200 Btu/h
This unit at 5°F median across its pairings
24,200 Btu/h
Median of 2.5-ton central models at 5°F
22,400 Btu/h
Models in this group
288

This unit is above 61% of them, at number 113 of 288 by heat at 5°F. The middle half of the group runs 14,250 to 30,000 Btu/h.

This size class is defined by cooling capacity, so cooling is not compared here.

Among 30,000 Btu central models, each by its median certified pairing, highest first: 5°F output as a share of its 47°F rating, 218th of 288 (tied); HSPF2, 177th of 290 (tied). Models without that figure are left out.

Similar ratings at 47°F

These central models share the nominal cooling size. Comparisons use each model’s median certified figures across pairings.

  • YOHA2-60CB: 46,000 Btu/h at 47°F (this model: 47,000); 32,400 Btu/h at 5°F (this model: 24,200).
  • KUSXA361A: 37,000 Btu/h at 47°F (this model: 47,000); 33,000 Btu/h at 5°F (this model: 24,200).
  • 284ANV036*0**B*: 35,200 Btu/h at 47°F (this model: 47,000); HSPF2 9.0 (this model: 8.1).

Closest models by heat at 5°F

Every 30,000 Btu (2.5-ton) unit, ranked by cooling efficiency, then heating efficiency

Floor area at the cold test point

The median certified output of 24,200 Btu/h at 5°F matches the size calculator’s heating estimate for these floor areas, rounded to about 10 sq ft. Each range divides that output by the climate band’s heating rates.

Floor area by climate band and house condition
Climate bandHouse conditionBtu/h per sq ftApproximate sq ft
MildDrafty, little insulation24–42580–1,010
MildTypical16–26930–1,510
MildTight, well insulated10–181,340–2,420
ColdDrafty, little insulation28–52470–860
ColdTypical18–30810–1,340
ColdTight, well insulated12–221,100–2,020
Very coldDrafty, little insulation32–58420–760
Very coldTypical22–38640–1,100
Very coldTight, well insulated16–28860–1,510

This is an estimate, not a house-specific load calculation. Output stays at the 5°F test point for every band; it does not predict output at the band’s winter design temperature.

Certified values for HVH837GKA2

209 pairings · 209 AHRI certificates

This pairing is the one shown above. Under all pairings, a single figure means every pairing agrees and a range means the pairing decides.

Certified values for HVH837GKA2
This pairingAll pairings
Heating
Heat output at 47°F high stage 46,500 Btu/h 46,000–48,000 Btu/h
Heat output at 17°F full speed 30,400 Btu/h 30,200–31,000 Btu/h
Heat output at 5°F full speed 24,200 Btu/h 24,000–24,400 Btu/h
Heat output below 5°F NR NR
Cold output 5°F output as a % of the 47°F rating 52%
COP at 5°F full speed 1.96 1.94–1.98
HSPF2 Region IV 8.1 8.1–8.5
Cooling
Cooling capacity at 95°F full-load test 32,600 Btu/h 31,600–33,000 Btu/h
EER2 at 95°F 11.7 11.7–12.0
SEER2 cooling season 17.5 17.0–18.0
Cooling at other temperatures NR NR
Equipment and listing
Refrigerant R-410A
Compressor Two-stage
Indoor unit EA*4X60L24A* 9 indoor units
Furnace*96VSN1202422A* 14 furnaces
Cold-climate designation EPA's designation, as published NC NC
ENERGY STAR Most Efficient EPA's designation, as published No On no pairings
Where it is sold US and Canada US and Canada
Model string as certified HVH837GKA2*+TSTAT

Across 209 certified pairings with 9 indoor models: heat at 5°F 24,000 Btu/h with EA*4X60L24A* to 24,400 Btu/h with EA*4X37L21A*; HSPF2 8.1 with EA*4X60L24A* to 8.5 with EA*4X37L21A*; SEER2 17.0 with EA*4X61L21A* to 18.0 with EA*4X60L24A*. Endpoints name one indoor model where recorded; the furnace pairing can also change the figures.

Pairings, by indoor-unit class

9 indoor units · 209 certified pairings

One row per indoor unit certified with this outdoor unit.

Furnace paired · 9 indoor units

  1. EN(A,D,W)4X60L24** brand not stated 24,000 Btu/hat 5°F, full speed

    47 pairings, 12 with a furnace · 47°F 47,000 Btu/h · 95°F cooling 32,200 Btu/h · Cold output 51% · COP 1.94

  2. EN(A,D)4X48L24** brand not stated 24,200 Btu/hat 5°F, full speed

    38 pairings, 12 with a furnace · 47°F 47,500 Btu/h · 95°F cooling 31,800 Btu/h · Cold output 51% · COP 1.94

  3. EA*4X61L24A* brand not stated 24,200 Btu/hat 5°F, full speed

    36 pairings, 12 with a furnace · 47°F 46,500 Btu/h · 95°F cooling 32,800 Btu/h · Cold output 52% · COP 1.96

  4. EN(A,D,W)4X48L21** brand not stated 24,200 Btu/hat 5°F, full speed

    31 pairings, 10 with a furnace · 47°F 47,500 Btu/h · 95°F cooling 31,800 Btu/h · Cold output 51% · COP 1.94

  5. EA*4X61L21A* brand not stated 24,300 Btu/hat 5°F, full speed

    24 pairings, 8 with a furnace · 47°F 46,500 Btu/h · 95°F cooling 32,800 Btu/h · Cold output 52% · COP 1.96

  6. EA*4X60L24A* (the pairing on screen) brand not stated 24,000 Btu/hat 5°F, full speed

    21 pairings, 7 with a furnace · 47°F 46,000 Btu/h · 95°F cooling 32,200 Btu/h · Cold output 52% · COP 1.96

  7. EHD4X60AAL brand not stated 24,200 Btu/hat 5°F, full speed

    6 pairings, 2 with a furnace · 47°F 46,750 Btu/h · 95°F cooling 32,500 Btu/h · Cold output 52% · COP 1.98

  8. EA*4X37L21A* brand not stated 24,400 Btu/hat 5°F, full speed

    3 pairings, 1 with a furnace · 47°F 47,500 Btu/h · 95°F cooling 32,200 Btu/h · Cold output 51% · COP 1.98

  9. EA*4X43L21A* brand not stated 24,400 Btu/hat 5°F, full speed

    3 pairings, 1 with a furnace · 47°F 47,500 Btu/h · 95°F cooling 32,200 Btu/h · Cold output 51% · COP 1.98

Indoor units in the furnace paired class
Indoor unit Brand At 5°FBtu/h · full speed At 47°FBtu/h · high stage At 95°FBtu/h · cooling Cold output% of 47°F rating COP 5°Ffull speed Cold climate Pairings
EN(A,D,W)4X60L24** — 24,000 47,000 32,200 51% 1.94 NC 47
EN(A,D)4X48L24** — 24,200 47,500 31,800 51% 1.94 NC 38
EA*4X61L24A* — 24,200 46,500 32,800 52% 1.96 NC 36
EN(A,D,W)4X48L21** — 24,200 47,500 31,800 51% 1.94 NC 31
EA*4X61L21A* — 24,300 46,500 32,800 52% 1.96 NC 24
EA*4X60L24A* (the pairing on screen) — 24,000 46,000 32,200 52% 1.96 NC 21
EHD4X60AAL — 24,200 46,750 32,500 52% 1.98 NC 6
EA*4X37L21A* — 24,400 47,500 32,200 51% 1.98 NC 3
EA*4X43L21A* — 24,400 47,500 32,200 51% 1.98 NC 3

The share is heat output at 5°F divided by the 47°F rating.

Showing 9 of 9 indoor units All 209 certified pairings

Sold as, and units with identical certified values

Brands listing this model number

Other brands that list these model numbers

Model number as listed

Variants of the same model number

5 units in this group. Basis: identical certified values in the certified data. This grouping is our inference, not a field in the certified data.

4 of 5 shown.

History and definitions

History

First certified record
Most recent certified record
Measurements reported
May 15, 2025
Status
In the certified data

Field definitions

COP
Heat delivered for each unit of electricity used. A COP of 2.5 gives 2.5 times the heat of an electric baseboard heater.
HSPF2
Heating efficiency over a typical season. Higher uses less electricity.
SEER2
Cooling efficiency over a typical season. Higher uses less electricity.
EER2
Cooling output divided by electrical input in the 95°F full-load test, in Btu/h per watt.
Cold output
Heat output at 5°F as a percentage of the 47°F rating.
% of rating at 17°F
Heat output at 17°F as a percentage of the 47°F rating.

NR not in the certified dataNC not cold-climate certifiedSP single pairing onlyVP varies by pairing; see the pairings tableWD withdrawn since the certified data was last read

Cite or print this page

Heat Pump List, “HVH837GKA2 — certified heat output”. Certified figures dated , checked daily.
https://heatpumplist.com/model/hvh837gka2