C5H8T60*K*AAA*

C5H8T60*K*AAA* is in the certified data.

Its certified full-speed heating output at 5°F is 29,600–31,800 Btu/h, 51–53% of its 47°F rating, depending on the pairing.

Comfortmaker, Day & Night + 1 more · central heat pump

All 173 certified Comfortmaker models · All 177 certified Day & Night models · All 175 certified Keeprite models

C5H8T60*K*AAA* is in the certified data as of Sep 19, 2026.

255 certified pairings with 64 different figures. See all

Certified heating and cooling

Heating at 47°F

57,500

36,800 at 17°F

30,200 at 5°F

Btu/h, certified

2.22 COP at 5°F

Cooling at 95°F

55,500

Btu/h, certified

EER2 11.7 at 95°F

SEER2 16.0

Heating and cooling by outdoor temperature

Certified heating at 5, 17, and 47°F and cooling at 95°F for C5H8T60*K*AAA*, by outdoor temperature Heating: 30,200 Btu/h at 5°F, 36,800 Btu/h at 17°F, 57,500 Btu/h at 47°F. Cooling: 55,500 Btu/h at 95°F. The bars start at zero. Median of 4.5-ton central models: 40,000 Btu/h at 5°F, 37,800 Btu/h at 17°F, 56,000 Btu/h at 47°F, 55,000 Btu/h at 95°F. 0 20,000 40,000 60,000 80,000 Btu/h 30,200 5°F 36,800 17°F 57,500 47°F 55,500 95°F Outdoor temperature (°F)
  • Heating output
  • Cooling output
  • Median of 4.5-ton central models
  • Example heating load
  • Example cooling load
  • Frosting range, 17 to 45°F

This pairing delivers 57,500 Btu/h of heat at 47°F, 36,800 Btu/h at 17°F, and 30,200 Btu/h at 5°F, 53% of its 47°F rating. It delivers 55,500 Btu/h of cooling at 95°F. At 5°F that is 9,800 Btu/h short of the example heating load of 40,000 Btu/h; at 95°F it is 35,500 Btu/h above the example cooling load of 20,000 Btu/h.

Each bar is a separate certified test, drawn at its outdoor temperature, starting at zero. The 47°F figure is at high stage; the 17 and 5°F figures are at full speed. The short dark line on each bar is the median of 4.5-ton central models, one value per model. The shaded 17 to 45°F band is the frosting range: the outdoor coil can frost, and the unit pauses to defrost.

The dashed lines are example loads for a typical area of about 1,650 sq ft where winters reach 5°F: heating runs from 40,000 Btu/h at 5°F to 0 at 65°F, and cooling runs from 0 at 65°F to 20,000 Btu/h at 95°F, at 1,000 sq ft per ton. A house in a hot climate or with large west-facing windows can need twice as much cooling. They are examples, not your building.

Calculate heating and cooling for your house

AHRI certificate 216348529 · listed by Comfortmaker · certified Jul 16, 2026 · 12 pairings share these values

Rebates where you live

Meets the recorded equipment thresholds of 29 programs in 18 states, provinces, or territories:California (2), Colorado (1), Delaware (1), Idaho (1), Kansas (1), Maryland (3), Michigan (2), Minnesota (2), Mississippi (1), Nevada (1), New Jersey (4), North Carolina (1), Oregon (2), Pennsylvania (3), South Carolina (1), Texas (3), Utah (1), Newfoundland and Labrador (1).

All 29 programs by state and province

California

Colorado

Delaware

Idaho

Kansas

Maryland

Michigan

Minnesota

Mississippi

Nevada

New Jersey

North Carolina

Oregon

Pennsylvania

South Carolina

Texas

Utah

Newfoundland and Labrador

Threshold comparisons use the unit’s median certified figures across its pairings, not the pairing selected above. Meeting these thresholds means the equipment may qualify; it does not guarantee approval. Service-area, installation, and product-list requirements also apply.

All rebate programs and their published thresholds

Certified output and power use

Certified output for the selected pairingThe four bars share one scale. The comparison is with the median of 4.5-ton central models. Heating tests run at 70°F indoors. The cooling test runs at 80°F indoors.
Outdoor temperature Certified outputBtu/h One scale vs class median COPat 5°F
5°Fone compressor speed 30,2008.85 kW −25% 2.22
17°Fone compressor speed 36,80010.79 kW −3% NR
47°Fone compressor speed 57,50016.85 kW +3% NR
95°Fcooling, full load 55,50016.27 kW — NR

EER2 11.7 in that test. SEER2 16.0 over the modeled cooling season.

Power use at each temperature

Electrical input in the 5°F full-speed test
3.99kW
Electrical input in the 95°F cooling test
4.74kW
Seasonal average heating COP
2.29

These exclude backup resistance heat.

Updated Sep 19, 2026 · Methodology

How it compares with other 54,000 Btu heat pumps

4.5-ton central models

This pairing at 5°F
30,200 Btu/h
This unit at 5°F median across its pairings
30,200 Btu/h
Median of 4.5-ton central models at 5°F
40,000 Btu/h
Models in this group
343

This unit is above 17% of them, at number 286 of 343 by heat at 5°F. The middle half of the group runs 32,000 to 45,000 Btu/h.

This size class is defined by cooling capacity, so cooling is not compared here.

Among 54,000 Btu central models, each by its median certified pairing, highest first: 5°F output as a share of its 47°F rating, 289th of 343 (tied); HSPF2, 291st of 358 (tied). Models without that figure are left out.

Similar ratings at 47°F

These central models share the nominal cooling size. Comparisons use each model’s median certified figures across pairings.

  • MDPH18060D: 57,000 Btu/h at 47°F (this model: 57,500); 51,000 Btu/h at 5°F (this model: 30,200).
  • AC060BXUPCH: 57,000 Btu/h at 47°F (this model: 57,500); 48,000 Btu/h at 5°F (this model: 30,200).
  • MDPH180604: 57,000 Btu/h at 47°F (this model: 57,500); 45,000 Btu/h at 5°F (this model: 30,200).

Closest models by heat at 5°F

Every 54,000 Btu (4.5-ton) unit, ranked by cooling efficiency, then heating efficiency

Floor area at the cold test point

The median certified output of 30,200 Btu/h at 5°F matches the size calculator’s heating estimate for these floor areas, rounded to about 10 sq ft. Each range divides that output by the climate band’s heating rates.

Floor area by climate band and house condition
Climate bandHouse conditionBtu/h per sq ftApproximate sq ft
MildDrafty, little insulation24–42720–1,260
MildTypical16–261,160–1,890
MildTight, well insulated10–181,680–3,020
ColdDrafty, little insulation28–52580–1,080
ColdTypical18–301,010–1,680
ColdTight, well insulated12–221,370–2,520
Very coldDrafty, little insulation32–58520–940
Very coldTypical22–38790–1,370
Very coldTight, well insulated16–281,080–1,890

This is an estimate, not a house-specific load calculation. Output stays at the 5°F test point for every band; it does not predict output at the band’s winter design temperature.

Certified values for C5H8T60*K*AAA*

255 pairings · 255 AHRI certificates

This pairing is the one shown above. Under all pairings, a single figure means every pairing agrees and a range means the pairing decides.

Certified values for C5H8T60*K*AAA*
This pairingAll pairings
Heating
Heat output at 47°F high stage 57,500 Btu/h 56,500–61,500 Btu/h
Heat output at 17°F full speed 36,800 Btu/h 36,200–38,500 Btu/h
Heat output at 5°F full speed 30,200 Btu/h 29,600–31,800 Btu/h
Heat output below 5°F NR NR
Cold output 5°F output as a % of the 47°F rating 53%
COP at 5°F full speed 2.22 2.18–2.36
HSPF2 Region IV 7.8 7.8–8.5
Cooling
Cooling capacity at 95°F full-load test 55,500 Btu/h 54,000–58,000 Btu/h
EER2 at 95°F 11.7 11.7–13.0
SEER2 cooling season 16.0 15.5–17.5
Cooling at other temperatures NR NR
Equipment and listing
Refrigerant R-454B
Compressor Two-stage
Indoor unit EA*5X61M21A* 12 indoor units
Furnace*95MSU1002120A* 20 furnaces
Cold-climate designation EPA's designation, as published NC NC
ENERGY STAR Most Efficient EPA's designation, as published No On no pairings
Where it is sold US and Canada US and Canada
Model string as certified C5H8T60*K*AAA*

Across 255 certified pairings with 12 indoor models: heat at 5°F 29,600 Btu/h with EA*5X60M24A* to 31,800 Btu/h with EVD5X61M24A*; HSPF2 7.8 with EA*5X60M24A* to 8.5 with EVD5X61M24A*; SEER2 15.5 with EA*5X60M24A* to 17.5 with FCMA5B60L0D*+WALLCON. Endpoints name one indoor model where recorded; the furnace pairing can also change the figures.

Pairings, by indoor-unit class

12 indoor units · 255 certified pairings

One row per indoor unit certified with this outdoor unit.

Furnace paired · 9 indoor units

  1. EA*5X60M24A* brand not stated 29,800 Btu/hat 5°F, full speed

    54 pairings, 18 with a furnace · 47°F 57,000 Btu/h · 95°F cooling 54,500 Btu/h · Cold output 52% · COP 2.22

  2. EA*5X61M24A* brand not stated 30,200 Btu/hat 5°F, full speed

    54 pairings, 18 with a furnace · 47°F 57,500 Btu/h · 95°F cooling 56,000 Btu/h · Cold output 53% · COP 2.22

  3. EA*5X61M21A* (the pairing on screen) brand not stated 30,200 Btu/hat 5°F, full speed

    45 pairings, 15 with a furnace · 47°F 57,500 Btu/h · 95°F cooling 55,500 Btu/h · Cold output 53% · COP 2.22

  4. EVD5X60M21A* brand not stated 30,400 Btu/hat 5°F, full speed

    27 pairings, 9 with a furnace · 47°F 58,000 Btu/h · 95°F cooling 54,000 Btu/h · Cold output 52% · COP 2.24

  5. EVM5X60M21A* brand not stated 30,000 Btu/hat 5°F, full speed

    24 pairings, 8 with a furnace · 47°F 57,500 Btu/h · 95°F cooling 54,000 Btu/h · Cold output 52% · COP 2.26

  6. EVD5X61M21A* brand not stated 31,000 Btu/hat 5°F, full speed

    21 pairings, 7 with a furnace · 47°F 59,000 Btu/h · 95°F cooling 55,000 Btu/h · Cold output 53% · COP 2.24

  7. EVM5X61M24A* brand not stated 31,700 Btu/hat 5°F, full speed

    12 pairings, 4 with a furnace · 47°F 60,000 Btu/h · 95°F cooling 55,750 Btu/h · Cold output 53% · COP 2.32

  8. EVD5X61M24A* brand not stated 31,700 Btu/hat 5°F, full speed

    6 pairings, 2 with a furnace · 47°F 60,000 Btu/h · 95°F cooling 56,000 Btu/h · Cold output 53% · COP 2.33

  9. EVM5X61M24A*+WALLCON brand not stated 30,800 Btu/hat 5°F, full speed

    3 pairings, 1 with a furnace · 47°F 59,000 Btu/h · 95°F cooling 55,500 Btu/h · Cold output 52% · COP 2.36

Indoor units in the furnace paired class
Indoor unit Brand At 5°FBtu/h · full speed At 47°FBtu/h · high stage At 95°FBtu/h · cooling Cold output% of 47°F rating COP 5°Ffull speed Cold climate Pairings
EA*5X60M24A* — 29,800 57,000 54,500 52% 2.22 NC 54
EA*5X61M24A* — 30,200 57,500 56,000 53% 2.22 NC 54
EA*5X61M21A* (the pairing on screen) — 30,200 57,500 55,500 53% 2.22 NC 45
EVD5X60M21A* — 30,400 58,000 54,000 52% 2.24 NC 27
EVM5X60M21A* — 30,000 57,500 54,000 52% 2.26 NC 24
EVD5X61M21A* — 31,000 59,000 55,000 53% 2.24 NC 21
EVM5X61M24A* — 31,700 60,000 55,750 53% 2.32 NC 12
EVD5X61M24A* — 31,700 60,000 56,000 53% 2.33 NC 6
EVM5X61M24A*+WALLCON — 30,800 59,000 55,500 52% 2.36 NC 3

Air handler · 1 indoor unit

  1. FCMA5B60L0D*+WALLCON brand not stated 30,200 Btu/hat 5°F, full speed

    3 pairings · 47°F 57,500 Btu/h · 95°F cooling 57,500 Btu/h · Cold output 53% · COP 2.30

Indoor units in the air handler class
Indoor unit Brand At 5°FBtu/h · full speed At 47°FBtu/h · high stage At 95°FBtu/h · cooling Cold output% of 47°F rating COP 5°Ffull speed Cold climate Pairings
FCMA5B60L0D*+WALLCON — 30,200 57,500 57,500 53% 2.30 NC 3

The share is heat output at 5°F divided by the 47°F rating.

Showing 10 of 12 indoor units All 255 certified pairings

Sold as, and units with identical certified values

Brands listing this model number

Other brands that list these model numbers

Model number as listed

Variants of the same model number

3 units in this group. Basis: identical certified values in the certified data. This grouping is our inference, not a field in the certified data.

2 of 3 shown.

Other model numbers with identical certified values

2 units share this record. Basis: identical certified values in the certified data. This grouping is our inference, not a field in the certified data.

1 of 2 shown.

Product history

  • C5H8T60*K*AAA* first appeared in the certified data between September 2024 and November 2024.

History and definitions

Other Mainline 18 SEER2 HP models by nominal cooling size: C5H8T24*K*AAA* (24,000 Btu), C5H8T36*K*AAA* (36,000 Btu), C5H8T48*K*AAA* (48,000 Btu).

History

First certified record
Most recent certified record
Measurements reported
Jul 16, 2026
Status
In the certified data

Field definitions

COP
Heat delivered for each unit of electricity used. A COP of 2.5 gives 2.5 times the heat of an electric baseboard heater.
HSPF2
Heating efficiency over a typical season. Higher uses less electricity.
SEER2
Cooling efficiency over a typical season. Higher uses less electricity.
EER2
Cooling output divided by electrical input in the 95°F full-load test, in Btu/h per watt.
Cold output
Heat output at 5°F as a percentage of the 47°F rating.
% of rating at 17°F
Heat output at 17°F as a percentage of the 47°F rating.

NR not in the certified dataNC not cold-climate certifiedSP single pairing onlyVP varies by pairing; see the pairings tableWD withdrawn since the certified data was last read

Cite or print this page

Heat Pump List, “C5H8T60*K*AAA* — certified heat output”. Certified figures dated , checked daily.
https://heatpumplist.com/model/c5h8t60_stk_staaa_st