HH860E2S12

HH860E2S12 is in the certified data.

Its certified full-speed heating output at 5°F is 33,600–40,000 Btu/h, 71–80% of its 47°F rating (tests at different compressor speeds), depending on the pairing.

Champion, Coleman + 4 more · central heat pump

All 48 certified Champion models · All 66 certified Coleman models · All 47 certified Fraser-Johnston models · All 179 certified Kenmore models · All 64 certified Luxaire models · All 105 certified York models

HH860E2S12 is in the certified data as of Oct 18, 2026.

2,207 certified pairings with 84 different figures. See all

Certified heating and cooling

Heating at 47°F

44,500

41,000 at 17°F

34,400 at 5°F

Btu/h, certified

2.20 COP at 5°F

Cooling at 95°F

44,000

Btu/h, certified

EER2 11.7 at 95°F

SEER2 17.5

Heating and cooling by outdoor temperature

Certified heating at 5, 17, and 47°F and cooling at 95°F for HH860E2S12, by outdoor temperature Heating: 34,400 Btu/h at 5°F, 41,000 Btu/h at 17°F, 44,500 Btu/h at 47°F. Cooling: 44,000 Btu/h at 95°F. The bars start at zero. Median of 3.5-ton central models: 33,000 Btu/h at 5°F, 31,000 Btu/h at 17°F, 44,000 Btu/h at 47°F, 44,000 Btu/h at 95°F. 0 20,000 40,000 60,000 Btu/h 34,400 5°F 41,000 17°F 44,500 47°F 44,000 95°F Outdoor temperature (°F)
  • Heating output
  • Cooling output
  • Median of 3.5-ton central models
  • Example heating load
  • Example cooling load
  • Frosting range, 17 to 45°F

This pairing delivers 44,500 Btu/h of heat at 47°F, 41,000 Btu/h at 17°F, and 34,400 Btu/h at 5°F, 77% of its 47°F rating. It delivers 44,000 Btu/h of cooling at 95°F. At 5°F that is 1,400 Btu/h above the example heating load of 33,000 Btu/h; at 95°F it is 27,000 Btu/h above the example cooling load of 17,000 Btu/h.

Each bar is a separate certified test, drawn at its outdoor temperature, starting at zero. The 47°F figure is at high stage; the 17 and 5°F figures are at full speed. The short dark line on each bar is the median of 3.5-ton central models, one value per model. The shaded 17 to 45°F band is the frosting range: the outdoor coil can frost, and the unit pauses to defrost.

The dashed lines are example loads for a typical area of about 1,400 sq ft where winters reach 5°F: heating runs from 33,000 Btu/h at 5°F to 0 at 65°F, and cooling runs from 0 at 65°F to 17,000 Btu/h at 95°F, at 1,000 sq ft per ton. A house in a hot climate or with large west-facing windows can need twice as much cooling. They are examples, not your building.

Calculate heating and cooling for your house

AHRI certificate 218688091 · listed by York · certified Oct 16, 2026 · 26 pairings share these values

Rebates where you live

Meets the recorded equipment thresholds of 43 programs in 25 states, provinces, or territories:California (2), Colorado (2), Connecticut (3), Delaware (1), Idaho (2), Illinois (1), Kansas (1), Maryland (3), Massachusetts (3), Michigan (2), Minnesota (3), Mississippi (1), Nevada (1), New Hampshire (3), New Jersey (4), North Carolina (1), Oregon (2), Pennsylvania (3), Rhode Island (1), South Carolina (1), Texas (3), Utah (1), Washington (3), Wisconsin (1), Newfoundland and Labrador (1).

All 43 programs by state and province

California

Colorado

Connecticut

Delaware

Idaho

Illinois

Kansas

Maryland

Massachusetts

Michigan

Minnesota

Mississippi

Nevada

New Hampshire

New Jersey

North Carolina

Oregon

Pennsylvania

Rhode Island

South Carolina

Texas

Utah

Washington

Wisconsin

Newfoundland and Labrador

Threshold comparisons use the unit’s median certified figures across its pairings, not the pairing selected above. Meeting these thresholds means the equipment may qualify; it does not guarantee approval. Service-area, installation, and product-list requirements also apply.

All rebate programs and their published thresholds

Certified output and power use

Certified output for the selected pairingThe four bars share one scale. The comparison is with the median of 3.5-ton central models. Heating tests run at 70°F indoors. The cooling test runs at 80°F indoors.
Outdoor temperature Certified outputBtu/h One scale vs class median COPat 5°F
5°Ffull speed 34,40010.08 kW +4% 2.20
17°Ffull speed 41,00012.02 kW +32% NR
47°Fhigh stage 44,50013.04 kW +1% NR
95°Fcooling, full load 44,00012.90 kW — NR

EER2 11.7 in that test. SEER2 17.5 over the modeled cooling season.

Power use at each temperature

Electrical input in the 5°F full-speed test
4.58kW
Electrical input in the 95°F cooling test
3.76kW
Seasonal average heating COP
2.37

These exclude backup resistance heat.

Updated Oct 18, 2026 · Methodology

How it compares with other 42,000 Btu heat pumps

3.5-ton central models

This pairing at 5°F
34,400 Btu/h
This unit at 5°F median across its pairings
34,400 Btu/h
Median of 3.5-ton central models at 5°F
33,000 Btu/h
Models in this group
222

This unit is above 55% of them, at number 99 of 222 by heat at 5°F. The middle half of the group runs 20,000 to 40,000 Btu/h.

This size class is defined by cooling capacity, so cooling is not compared here.

Among 42,000 Btu central models, each by its median certified pairing, highest first: 5°F output as a share of its 47°F rating, 93rd of 222; HSPF2, 122nd of 224 (tied). Models without that figure are left out.

Similar ratings at 47°F

These central models share the nominal cooling size. Comparisons use each model’s median certified figures across pairings.

  • SL22KLV-048-230A: The same 45,000 Btu/h rating at 47°F; 44,000 Btu/h at 5°F (this model: 34,400).
  • KUSXA422A: The same 45,000 Btu/h rating at 47°F; 42,000 Btu/h at 5°F (this model: 34,400).
  • SOV48H2BA: The same 45,000 Btu/h rating at 47°F; 40,000 Btu/h at 5°F (this model: 34,400).

Closest models by heat at 5°F

Every 42,000 Btu (3.5-ton) unit, ranked by cooling efficiency, then heating efficiency

Floor area at the cold test point

The median certified output of 34,400 Btu/h at 5°F matches the size calculator’s heating estimate for these floor areas, rounded to about 10 sq ft. Each range divides that output by the climate band’s heating rates.

Floor area by climate band and house condition
Climate bandHouse conditionBtu/h per sq ftApproximate sq ft
MildDrafty, little insulation24–42820–1,430
MildTypical16–261,320–2,150
MildTight, well insulated10–181,910–3,440
ColdDrafty, little insulation28–52660–1,230
ColdTypical18–301,150–1,910
ColdTight, well insulated12–221,560–2,870
Very coldDrafty, little insulation32–58590–1,080
Very coldTypical22–38910–1,560
Very coldTight, well insulated16–281,230–2,150

This is an estimate, not a house-specific load calculation. Output stays at the 5°F test point for every band; it does not predict output at the band’s winter design temperature.

Certified values for HH860E2S12

2,207 pairings · 2,207 AHRI certificates

This pairing is the one shown above. Under all pairings, a single figure means every pairing agrees and a range means the pairing decides.

Certified values for HH860E2S12
This pairingAll pairings
Heating
Heat output at 47°F high stage 44,500 Btu/h 44,000–53,500 Btu/h
Heat output at 17°F full speed 41,000 Btu/h 40,000–45,500 Btu/h
Heat output at 5°F full speed 34,400 Btu/h 33,600–40,000 Btu/h
Heat output below 5°F NR NR
Cold output 5°F output as a % of the 47°F rating 77%
COP at 5°F full speed 2.20 2.00–2.32
HSPF2 Region IV 8.1 8.1–8.5
Cooling
Cooling capacity at 95°F full-load test 44,000 Btu/h 43,500–54,000 Btu/h
EER2 at 95°F 11.7 11.0–12.0
SEER2 cooling season 17.5 15.2–18.0
Cooling at other temperatures NR NR
Equipment and listing
Refrigerant R-454B
Compressor Two-stage
Indoor unit CTF60C5CGS2 47 indoor units
FurnaceTM9V100C20MP12 137 furnaces
Cold-climate designation EPA's designation, as published NC On some pairings
ENERGY STAR Most Efficient EPA's designation, as published Yes On some pairings
Where it is sold US and Canada US and Canada
Model string as certified HH860E2S12

Across 2,207 certified pairings with 47 indoor models: heat at 5°F 33,600 Btu/h with CTF60C5CGS1 to 40,000 Btu/h with CTM60D5CJS2; HSPF2 8.1 with CTF60C5CGS1 to 8.5 with CTF60D5CGS2+JME18D2SN2; SEER2 15.2 with CTF60C5CGS1 to 18.0 with JHC60C5CH2SS1. Endpoints name one indoor model where recorded; the furnace pairing can also change the figures.

Pairings, by indoor-unit class

47 indoor units · 2,207 certified pairings

One row per indoor unit certified with this outdoor unit.

Furnace paired · 2 indoor units

  1. CTF60D5CJS2 brand not stated 39,000 Btu/hat 5°F, full speed

    42 pairings, 18 with a furnace · 47°F 52,500 Btu/h · 95°F cooling 53,500 Btu/h · Cold output 74% · COP 2.26

  2. CTM60D5CJS2 brand not stated 39,000 Btu/hat 5°F, full speed

    37 pairings, 17 with a furnace · 47°F 52,500 Btu/h · 95°F cooling 53,500 Btu/h · Cold output 74% · COP 2.28

Indoor units in the furnace paired class
Indoor unit Brand At 5°FBtu/h · full speed At 47°FBtu/h · high stage At 95°FBtu/h · cooling Cold output% of 47°F rating COP 5°Ffull speed Cold climate Pairings
CTF60D5CJS2 — 39,000 52,500 53,500 74% 2.26 NC 42
CTM60D5CJS2 — 39,000 52,500 53,500 74% 2.28 NC 37

Air handler · 8 indoor units

  1. CTM60C5CGS2 brand not stated 34,200 Btu/hat 5°F, full speed

    309 pairings, 119 with a furnace · 47°F 45,000 Btu/h · 95°F cooling 44,500 Btu/h · Cold output 77% · COP 2.22

  2. CTF60C5CGS2 (the pairing on screen) brand not stated 34,200 Btu/hat 5°F, full speed

    296 pairings, 114 with a furnace · 47°F 45,000 Btu/h · 95°F cooling 44,500 Btu/h · Cold output 77% · COP 2.22

  3. CTU60C5XGS2+TXV brand not stated 34,200 Btu/hat 5°F, full speed

    296 pairings, 114 with a furnace · 47°F 45,000 Btu/h · 95°F cooling 44,500 Btu/h · Cold output 77% · COP 2.22

  4. CTF60C5CGS1 brand not stated 34,200 Btu/hat 5°F, full speed

    270 pairings, 104 with a furnace · 47°F 45,000 Btu/h · 95°F cooling 44,500 Btu/h · Cold output 77% · COP 2.22

  5. CTM60C5CGS1 brand not stated 34,400 Btu/hat 5°F, full speed

    270 pairings, 104 with a furnace · 47°F 45,000 Btu/h · 95°F cooling 44,500 Btu/h · Cold output 77% · COP 2.24

  6. CTU60C5XGS1+TXV brand not stated 34,200 Btu/hat 5°F, full speed

    270 pairings, 104 with a furnace · 47°F 45,000 Btu/h · 95°F cooling 44,500 Btu/h · Cold output 77% · COP 2.22

  7. CTF60D5CGS2 brand not stated 34,400 Btu/hat 5°F, full speed

    48 pairings, 18 with a furnace · 47°F 45,500 Btu/h · 95°F cooling 45,000 Btu/h · Cold output 77% · COP 2.24

  8. CTM60D5CGS2 brand not stated 35,100 Btu/hat 5°F, full speed

    48 pairings, 18 with a furnace · 47°F 45,500 Btu/h · 95°F cooling 44,750 Btu/h · Cold output 77% · COP 2.24

Indoor units in the air handler class
Indoor unit Brand At 5°FBtu/h · full speed At 47°FBtu/h · high stage At 95°FBtu/h · cooling Cold output% of 47°F rating COP 5°Ffull speed Cold climate Pairings
CTM60C5CGS2 — 34,200 45,000 44,500 77% 2.22 NC 309
CTF60C5CGS2 (the pairing on screen) — 34,200 45,000 44,500 77% 2.22 NC 296
CTU60C5XGS2+TXV — 34,200 45,000 44,500 77% 2.22 NC 296
CTF60C5CGS1 — 34,200 45,000 44,500 77% 2.22 NC 270
CTM60C5CGS1 — 34,400 45,000 44,500 77% 2.24 NC 270
CTU60C5XGS1+TXV — 34,200 45,000 44,500 77% 2.22 NC 270
CTF60D5CGS2 — 34,400 45,500 45,000 77% 2.24 NC 48
CTM60D5CGS2 — 35,100 45,500 44,750 77% 2.24 NC 48

The share is heat output at 5°F divided by the 47°F rating.

Showing 10 of 47 indoor units All 2,207 certified pairings

Sold as, and units with identical certified values

History and definitions

Other LX SERIES models by nominal cooling size: THF2B18S21 (18,000 Btu), HH824E2S11 (24,000 Btu), HH824E2S12 (24,000 Btu), PHE6A2424 (24,000 Btu), PHG6A240752X4 (24,000 Btu), THF2B24T21 (24,000 Btu), HH836E2S12 (30,000 Btu), THF2B30T21 (30,000 Btu); more models from this brand.

Other LX SERIES models by nominal cooling size: HH824E2S11 (24,000 Btu), HH824E2S12 (24,000 Btu), HH836E2S12 (30,000 Btu), HH836E2S11 (36,000 Btu), HH860E2S11 (42,000 Btu).

Other LX SERIES models by nominal cooling size: YH2F18SB21 (18,000 Btu), YH518E2S11 (18,000 Btu), YH618E2S11 (18,000 Btu), HH824E2S11 (24,000 Btu), HH824E2S12 (24,000 Btu), PHE6A2424 (24,000 Btu), YH2F24TB21 (24,000 Btu), YH524E2S11 (24,000 Btu); more models from this brand.

History

First certified record
Most recent certified record
Measurements reported
Oct 16, 2026
Status
In the certified data

Field definitions

COP
Heat delivered for each unit of electricity used. A COP of 2.5 gives 2.5 times the heat of an electric baseboard heater.
HSPF2
Heating efficiency over a typical season. Higher uses less electricity.
SEER2
Cooling efficiency over a typical season. Higher uses less electricity.
EER2
Cooling output divided by electrical input in the 95°F full-load test, in Btu/h per watt.
Cold output
Heat output at 5°F as a percentage of the 47°F rating.
% of rating at 17°F
Heat output at 17°F as a percentage of the 47°F rating.

NR not in the certified dataNC not cold-climate certifiedSP single pairing onlyVP varies by pairing; see the pairings tableWD withdrawn since the certified data was last read

Cite or print this page

Heat Pump List, “HH860E2S12 — certified heat output”. Certified figures dated , checked daily.