Heat Pump List

Tools

RD17AZ60AJ3N

RD17AZ60AJ3N is in the certified data.

Its certified full-speed heating output at 5°F is 48,500–49,500 Btu/h, 81–83% of its 47°F rating (tests at different compressor speeds), depending on the pairing.

Friedrich, Rheem + 3 more · central heat pump

All 121 certified Friedrich models · All 91 certified Rheem models · All 47 certified Russell models · All 89 certified Ruud models · All 51 certified Sure models

RD17AZ60AJ3N is in the certified data as of Sep 19, 2026. RD17AZ60AJ3N returned to the certified data between August 2025 and September 2026.

76 certified pairings with 5 different figures. See all

Certified heating and cooling

Heating at 47°F

60,000

50,500 at 17°F

49,500 at 5°F

Btu/h, certified

1.75 COP at 5°F

Cooling at 95°F

55,000

Btu/h, certified

EER2 10.0 at 95°F

SEER2 18.0

Heating and cooling by outdoor temperature

Certified heating at 5, 17, and 47°F and cooling at 95°F for RD17AZ60AJ3N, by outdoor temperature Heating: 49,500 Btu/h at 5°F, 50,500 Btu/h at 17°F, 60,000 Btu/h at 47°F. Cooling: 55,000 Btu/h at 95°F. The bars start at zero. Median of 4.5-ton central models: 40,000 Btu/h at 5°F, 37,800 Btu/h at 17°F, 56,000 Btu/h at 47°F, 55,000 Btu/h at 95°F. 0 20,000 40,000 60,000 Btu/h 49,500 5°F 50,500 17°F 60,000 47°F 55,000 95°F Outdoor temperature (°F)
  • Heating output
  • Cooling output
  • Median of 4.5-ton central models
  • Example heating load
  • Example cooling load
  • Frosting range, 17 to 45°F

This pairing delivers 60,000 Btu/h of heat at 47°F, 50,500 Btu/h at 17°F, and 49,500 Btu/h at 5°F, 83% of its 47°F rating. It delivers 55,000 Btu/h of cooling at 95°F. At 5°F that is 9,500 Btu/h above the example heating load of 40,000 Btu/h; at 95°F it is 35,000 Btu/h above the example cooling load of 20,000 Btu/h.

Each bar is a separate certified test, drawn at its outdoor temperature, starting at zero. The 47°F figure is at normal speed; the 17 and 5°F figures are at full speed. The short dark line on each bar is the median of 4.5-ton central models, one value per model. The shaded 17 to 45°F band is the frosting range: the outdoor coil can frost, and the unit pauses to defrost.

The dashed lines are example loads for a typical area of about 1,650 sq ft where winters reach 5°F: heating runs from 40,000 Btu/h at 5°F to 0 at 65°F, and cooling runs from 0 at 65°F to 20,000 Btu/h at 95°F, at 1,000 sq ft per ton. A house in a hot climate or with large west-facing windows can need twice as much cooling. They are examples, not your building.

Calculate heating and cooling for your house

AHRI certificate 214075320 · listed by RUSSELL · certified Jun 3, 2026 · 28 pairings share these values

Rebates where you live

Meets the recorded equipment thresholds of 39 programs in 30 states, provinces, or territories:Alabama (1), Arizona (1), California (2), Colorado (1), Connecticut (1), Delaware (1), Idaho (2), Illinois (1), Kansas (1), Kentucky (1), Maryland (3), Massachusetts (1), Michigan (2), Minnesota (3), Mississippi (2), Nevada (1), New Hampshire (2), New Jersey (2), New York (4), North Carolina (1), Oregon (2), Rhode Island (1), South Carolina (1), Tennessee (1), Texas (1), Utah (1), Vermont (3), Washington (3), Wisconsin (1), Newfoundland and Labrador (1).

All 39 programs by state and province

Alabama

Arizona

California

Colorado

Connecticut

Delaware

Idaho

Illinois

Kansas

Kentucky

Maryland

Massachusetts

Michigan

Minnesota

Mississippi

Nevada

New Hampshire

New Jersey

New York

North Carolina

Oregon

Rhode Island

South Carolina

Tennessee

Texas

Utah

Vermont

Washington

Wisconsin

Newfoundland and Labrador

Threshold comparisons use the unit’s median certified figures across its pairings, not the pairing selected above. Meeting these thresholds means the equipment may qualify; it does not guarantee approval. Service-area, installation, and product-list requirements also apply.

All rebate programs and their published thresholds

Certified output and power use

Certified output for the selected pairingThe four bars share one scale. The comparison is with the median of 4.5-ton central models. Heating tests run at 70°F indoors. The cooling test runs at 80°F indoors.
Outdoor temperature Certified outputBtu/h One scale vs class median COPat 5°F
5°Ffull speed 49,50014.51 kW +24% 1.75
17°Ffull speed 50,50014.80 kW +34% NR
47°Fnormal speed 60,00017.58 kW +7% NR
95°Fcooling, full load 55,00016.12 kW — NR

EER2 10.0 in that test. SEER2 18.0 over the modeled cooling season.

Power use at each temperature

Electrical input in the 5°F full-speed test
8.29kW
Electrical input in the 95°F cooling test
5.50kW
Seasonal average heating COP
2.37

These exclude backup resistance heat.

Updated Sep 19, 2026 · Methodology

How it compares with other 54,000 Btu heat pumps

4.5-ton central models

This pairing at 5°F
49,500 Btu/h
This unit at 5°F median across its pairings
49,500 Btu/h
Median of 4.5-ton central models at 5°F
40,000 Btu/h
Models in this group
343

This unit is above 92% of them, at number 28 of 343 by heat at 5°F. The middle half of the group runs 32,000 to 45,000 Btu/h.

This size class is defined by cooling capacity, so cooling is not compared here.

Among 54,000 Btu central models, each by its median certified pairing, highest first: 5°F output as a share of its 47°F rating, 50th of 343; HSPF2, 239th of 358 (tied). Models without that figure are left out.

Similar ratings at 47°F

These central models share the nominal cooling size. Comparisons use each model’s median certified figures across pairings.

  • HL19B6021: The same 60,000 Btu/h rating at 47°F; 32,600 Btu/h at 5°F (this model: 49,500).
  • DLCURAH60ABK: 59,000 Btu/h at 47°F (this model: 60,000); HSPF2 9.4 (this model: 8.1).
  • 27VPA960A*030*: 58,500 Btu/h at 47°F (this model: 60,000); 40,500 Btu/h at 5°F (this model: 49,500).

Closest models by heat at 5°F

Every 54,000 Btu (4.5-ton) unit, ranked by cooling efficiency, then heating efficiency

Floor area at the cold test point

The median certified output of 49,500 Btu/h at 5°F matches the size calculator’s heating estimate for these floor areas, rounded to about 10 sq ft. Each range divides that output by the climate band’s heating rates.

Floor area by climate band and house condition
Climate bandHouse conditionBtu/h per sq ftApproximate sq ft
MildDrafty, little insulation24–421,180–2,060
MildTypical16–261,900–3,090
MildTight, well insulated10–182,750–4,950
ColdDrafty, little insulation28–52950–1,770
ColdTypical18–301,650–2,750
ColdTight, well insulated12–222,250–4,130
Very coldDrafty, little insulation32–58850–1,550
Very coldTypical22–381,300–2,250
Very coldTight, well insulated16–281,770–3,090

This is an estimate, not a house-specific load calculation. Output stays at the 5°F test point for every band; it does not predict output at the band’s winter design temperature.

Certified values for RD17AZ60AJ3N

76 pairings · 76 AHRI certificates

This pairing is the one shown above. Under all pairings, a single figure means every pairing agrees and a range means the pairing decides.

Certified values for RD17AZ60AJ3N
This pairingAll pairings
Heating
Heat output at 47°F normal speed 60,000 Btu/h 60,000 Btu/h
Heat output at 17°F full speed 50,500 Btu/h 50,000–51,000 Btu/h
Heat output at 5°F full speed 49,500 Btu/h 48,500–49,500 Btu/h
Heat output below 5°F NR NR
Cold output 5°F output as a % of the 47°F rating 83%
COP at 5°F full speed 1.75 1.75
HSPF2 Region IV 8.1 8.1
Cooling
Cooling capacity at 95°F full-load test 55,000 Btu/h 55,000–55,500 Btu/h
EER2 at 95°F 10.0 10.0
SEER2 cooling season 18.0 17.0–19.0
Cooling at other temperatures NR NR
Equipment and listing
Refrigerant R-410A
Compressor Variable speed
Indoor unit TCFZ6024STANM 4 indoor units
FurnaceS951V1005A21UHU 50 furnaces
Cold-climate designation EPA's designation, as published Yes On every pairing
ENERGY STAR Most Efficient EPA's designation, as published No On no pairings
Where it is sold US and Canada US and Canada
Model string as certified RD17AZ60AJ3N

Across 76 certified pairings with 4 indoor models: heat at 5°F 48,500 Btu/h with FRH3VZ6024STACN to 49,500 Btu/h with RCFZ6024STANM; HSPF2 8.1 throughout; SEER2 17.0 with RCFZ6024STANM to 19.0 with FRH3VZ6024STACN. Endpoints name one indoor model where recorded; the furnace pairing can also change the figures.

Pairings, by indoor-unit class

4 indoor units · 76 certified pairings

One row per indoor unit certified with this outdoor unit.

Furnace paired · 2 indoor units

  1. TCFZ6024STANM (the pairing on screen) brand not stated 49,500 Btu/hat 5°F, full speed

    45 pairings, 30 with a furnace · 47°F 60,000 Btu/h · 95°F cooling 55,000 Btu/h · Cold output 83% · COP 1.75

  2. RCFZ6024STANM brand not stated 49,500 Btu/hat 5°F, full speed

    28 pairings, 20 with a furnace · 47°F 60,000 Btu/h · 95°F cooling 55,000 Btu/h · Cold output 83% · COP 1.75

Indoor units in the furnace paired class
Indoor unit Brand At 5°FBtu/h · full speed At 47°FBtu/h · normal speed At 95°FBtu/h · cooling Cold output% of 47°F rating COP 5°Ffull speed Cold climate Pairings
TCFZ6024STANM (the pairing on screen) — 49,500 60,000 55,000 83% 1.75 Yes 45
RCFZ6024STANM — 49,500 60,000 55,000 83% 1.75 Yes 28

Air handler · 2 indoor units

  1. RH3VZ6024STACN brand not stated 48,500 Btu/hat 5°F, full speed

    2 pairings · 47°F 60,000 Btu/h · 95°F cooling 55,500 Btu/h · Cold output 81% · COP 1.75

  2. FRH3VZ6024STACN brand not stated 48,500 Btu/hat 5°F, full speed

    1 pairing · 47°F 60,000 Btu/h · 95°F cooling 55,500 Btu/h · Cold output 81% · COP 1.75

Indoor units in the air handler class
Indoor unit Brand At 5°FBtu/h · full speed At 47°FBtu/h · normal speed At 95°FBtu/h · cooling Cold output% of 47°F rating COP 5°Ffull speed Cold climate Pairings
RH3VZ6024STACN — 48,500 60,000 55,500 81% 1.75 Yes 2
FRH3VZ6024STACN — 48,500 60,000 55,500 81% 1.75 Yes 1

The share is heat output at 5°F divided by the 47°F rating.

Showing 4 of 4 indoor units

Sold as, and units with identical certified values

Product history

  • RD17AZ60AJ3N returned to the certified data between August 2025 and September 2026.
  • RD17AZ60AJ3N changed its certified heat output at 47°F on 60 pairings in the certified data between September 2024 and September 2026. The new figure is higher on all 60.
  • RD17AZ60AJ3N changed its certified heat output at 47°F on 16 pairings in the certified data between November 2024 and September 2026. The new figure is higher on all 16.
  • RD17AZ60AJ3N was last in the certified data in records from November 2024; it was not in the list on Feb 1, 2025.
  • RD17AZ60AJ3N was in the certified data by September 2024.

History and definitions

Other F Series models by nominal cooling size: RD17AZ24AJ3N (24,000 Btu), RD17AZ36AJ3N (36,000 Btu), FWP14AY42AJ2N (42,000 Btu), RD17AZ48AJ3N (48,000 Btu), FRP14AY60AJ2N (54,000 Btu), FWP14AY60AJ2N (54,000 Btu).

Other PRESTIGE SERIES models by nominal cooling size: RD18AY24AJVC (18,000 Btu), RD17AZ24AJ3N (24,000 Btu), RP18AZ24AJVC (24,000 Btu), RP19AY24AJVC (24,000 Btu), RD18AY36AJVC (30,000 Btu), RD17AZ36AJ3N (36,000 Btu), RP18AZ36AJVC (36,000 Btu), RP19AY36AJVC (36,000 Btu); more models from this brand.

Other VANTIX models by nominal cooling size: RD18AY24AJVC (18,000 Btu), SP15AY18AJ2N (18,000 Btu), SP15AZ18AJ2N (18,000 Btu), RD16AY24AJVC (24,000 Btu), RD17AZ24AJ3N (24,000 Btu), SP15AZ24AJ2N (24,000 Btu), SP18AZ24AJVC (24,000 Btu), SP19AY24AJVC (24,000 Btu); more models from this brand.

History

First certified record
Most recent certified record
Measurements reported
Jun 3, 2026
Status
In the certified data

Field definitions

COP
Heat delivered for each unit of electricity used. A COP of 2.5 gives 2.5 times the heat of an electric baseboard heater.
HSPF2
Heating efficiency over a typical season. Higher uses less electricity.
SEER2
Cooling efficiency over a typical season. Higher uses less electricity.
EER2
Cooling output divided by electrical input in the 95°F full-load test, in Btu/h per watt.
Cold output
Heat output at 5°F as a percentage of the 47°F rating.
% of rating at 17°F
Heat output at 17°F as a percentage of the 47°F rating.

NR not in the certified dataNC not cold-climate certifiedSP single pairing onlyVP varies by pairing; see the pairings tableWD withdrawn since the certified data was last read

Cite or print this page

Heat Pump List, “RD17AZ60AJ3N — certified heat output”. Certified figures dated , checked daily.
https://heatpumplist.com/model/rd17az60aj3n